IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
15
>>
NOTE: Signal Circuits 1 and 2 located on the Operators
Display are Numbers 129 and 130, respectively.
10. The display will show the status of the signal circuit in respect to Walk Test. Use the
up/down arrow keys to toggle the signal circuit into and out of the Walk Test mode. When
you have made your selection press the “
Enter”
key to begin Walk Test.
11. The system will now enter the Walk Test Mode. The Acknowledge and Trouble LED’s will
flash and the buzzer will sound. The system will remain in Trouble until all Walk Test
devices are cleared from the system.
Status: Fault
XX/XX/94 xx:xx
System in Walk Test
Figure T6
∆∆∆∆
WARNING !
If the system is in Walk Test mode ,and a device not in the test
mode is activated, the system will go into alarm and all output
circuits will be activated.
12. To clear Walk Test operation select 4=Clear from the Walk Test Prog Menu to clear all
devices, individual devices may be cleared in the same manner as described in steps 1-10
above. Each device must be set to “NOT IN WALK TEST”.
13. If all devices have been cleared from Walk Test the system will return to the Idle Mode.
ByPass Mode
The ByPass function is used to remove an addressable device or signal circuit
from service. Bypassing a device will disable the control panel response from the
device selected or prevent activation of the device or signal circuit.
1.
From the Function Programming menu, press the “2” followed by the “Enter” key.
2.
Figure T7 is now displayed. The ByPass LED will flash at 60 PPM.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...