IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
33
SYSTEM RESTART / RE-CONFIGURATION - SMARTSTART
∆∆∆∆
WARNING !
All programming data will be lost when the system is re-
configured. The system will initialize the SmartStart
feature
and will configure a new data base.
Hardware Reset
1. Complete a hardware reset by shorting the jumper pins on P4, located on the CPU card. Figure 2
screen will be displayed. (Power On/System Reset)
2. While the Power On LED is still flashing, press the [
ACK
] switch. Figure 3 will be displayed.
Password Entry Screen
Enter Password:
Security Level: X
User ID: XXX
Figure 3
3. Enter a Level 4 password. If an invalid password is entered, or no password is entered, the system will
go into normal reset and skip the SmartStart.
4. If the password is accepted Figure 3A will be displayed. If no action is taken the system will continue its reset
process.
To Initialize System to Default settings
Press Enter Key Now
All Programmed Data will be lost !!!!
Figure 3A
∆∆∆∆
WARNING !
Pressing "Enter" - all programmed data will be lost. Pressing
any other key will Bypassed the re-configuration sequence.
5. Press "
Enter
" to begin SmartStart processing. Figure 3A is displayed. "Time remaining
N
sec" is a
countdown from 15 seconds.
Status : Normal
00/00/94 00:00
Begin System I/O Assignments.
Please Wait .... 15 sec Power Up Delay !
Time remaining N sec
Figure 3B
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...