IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
34
Hardware Reset (continued)
5. After a 15 second delay, the system commences a hardware restart. Modules and devices
are being read and will scroll up on the display, Figure 3C. Next the System RESET
screen is shown, Figure 2A. Then the "System Idle" screen is displayed, Figure 4.
Polling Card XXX Circuit XXX Address XXX
Polling Card XXX Circuit XXX Address XXX
Polling Card XXX Circuit XXX Address XXX
Polling Card XXX Circuit XXX Address XXX
Figure 3B
>>
NOTE: Upon completion of the SmartStart process, all
connected addresses will be contained in system memory and
all inputs will be tied to all outputs. Any input in Alarm will
activate the system outputs.
System Idle Display
After the initial system startup or system re-configuration is completed, the display will show
the current date (month/day/year) and time (military), see Figure 4.
>>
NOTE: The system is equipped with a built-in screen saver.
When the system remains in a idle mode (i.e. normal quiescent
condition) for over 15 seconds the screen will automatically go
blank.
Status :Normal
XX/XX/99 xx:xx
System Idle
Figure 4
PASSWORD ENTRY - ACCESS LEVELS
Four levels of password protection have been incorporated in the IF 610 system
firmware. These passwords allow access to various functions of the system. Each
of the four levels default to certain functions of the system and can be re-assigned to
other functions via programming. Up to ten passwords may be assigned to these
access levels. As well, an area to assign a user ID to each password has also been
provided for quick reference. Each user ID may contain up to 10 characters. Each
of these password ID’s may be assigned up to a ten character string.
>>
NOTE: System configuration (i.e. SmartStart
) defaults to level 2 password access.
When the password access level is changed, the system defaults to that level even when the
system loses power. The system will not default to a Level 4 .
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...