IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
46
Special
Signal Circuit
Functions
A. SIGNAL SILENCE INHIBIT
Silence Inhibit will prevent the operation of the Signal Silence function for a
programmable period ranging from 30 seconds to 5 minutes from the time
the first point goes into alarm. If the panel is programmed for Silence
Inhibit any activation of the Signal Silence Switch will be ignored, allowing
the output signal circuits to be active, until the programmed delay has
elapsed.
B. AUTO SILENCE - Automatic Signal Cutoff
If an output signaling circuit is programmed for Auto Silence it will
automatically silence the signal circuits, after the programmed delay, from
the time the first point goes into alarm. If subsequent to its silencing, a new
alarm occurs, the output signaling circuit will resound and the auto silence
time-out feature will reset its timer to silence its associated outputs after the
programmed delay.
C. Drillable
Any signal circuit programmed as drillable will activate when the drill
feature is activated.
Restoring Outputs
A. Restore On - ACKNOWLEDGE
For use with supplementary signaling and
functions
Any active output point programmed to restore on ACKNOWLEDGE will
return to Idle whenever the Acknowledge switch is Depressed. . All output
points that were returned to Idle will reactivate upon a subsequent alarm.
B. Restore On - RESET
Serves as System Back up. Any active output point not restored by any
other means will restore on RESET. Any active output programmed to
restore on RESET will not restore on any other action.
C. SEQUENTIAL RESTORE - Upon System Reset
The sequential restore only applies to relay outputs. Any active RCE-95
programmed for Sequential Restore will only restore on Reset, not on
Acknowledge. Selected relays will return to Idle 4 seconds apart, starting
with the highest address and ending at the lowest address set. The restore
sequence is determined by the actual address of the RCE and is not
programmable.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...