IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
48
CBE Programming
Control-by-Event "CBE" programming is dedicated to system wide ALARM functions.
Select "CBE" (#2) from the main "Programming Mode" menu to change or assign input
group assignment with the associated output group.
To select "logical" Group Inputs
1.
Select "CBE" (
2
) from the main "Programming Mode" menu.
2.
Press
"
Enter
".
Enter Input Group#: XXX
Figure 13
3.
Using numeric keys, enter the corresponding input group number. The
group number will be displayed in the location as shown in Figure 14.
xxx
Enter Input Group: xxx
Figure 14
4.
Enter all desired input group numbers. The assigned input group number
is displayed in top left of screen. As the next input group number is entered,
group numbers are sequentially arranged (ascending order). Enter up to 256
group input numbers.
>>
NOTE: To cancel an individual input group, enter that group number and
press "Enter". The group number is not shown and is then canceled.
xxx xxx xxx xxx xxx xxx xxx xxx xxx
xxx xxx xxx xxx xxx xxx xxx
Enter Input Group: xxx
Figure 14A
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...