Indicators
____________________________________________________________________________________________
POWER ON
Indication
The green "Power On" LED indicates AC line operation. If pulsing, this
indicates a problem with the incoming AC line voltage.
ALARM
The "Alarm" LED (red) indicates a common fire alarm has been activated in
the system.
PRE ALARM
The PreAlarm LED (red) indicates that the system is in a first stage alarm
condition , such as alarm verification.
DRILL
The Drill LED (yellow) indicates the Drill feature has been activated.
ACKNOWLEDGE
The Acknowledge LED (yellow) will flash to indicate the next action is to
press the "ACK" switch.
SUPERVISORY
ALARM
The Supervisory LED (yellow) indicates a supervisory zone has activated
(alarmed).
SIGNAL SILENCE
The Signal Silence LED (red) will flash to indicate that the signal silence
switch is active.
CITY TIE
The City Tie LED's are red for active, yellow for trouble.
SIGNAL CIRCUIT 1
Signal Circuit 1 LED's are red for active, yellow for trouble.
SIGNAL CIRCUIT 2
Signal Circuit 2 LED's are red for active, yellow for trouble.
RESET
The Reset LED's (red) flash when the reset switch is available for use.
TROUBLE
The Trouble LED (yellow) indicates the system is not in the normal
condition, a fault has been detected.
____________________________________________________________________________________________
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...