IdentiFlex 630 Installation and Operation Manual
S
mart
S
tart Capable
9-25-96
8
SYSTEM OPERATING CONDITIONS
Default Mode
WARNING NOTE
When shipped from the factory, the IdentiFlex 630 system has been initialized to
a minimal "default" configuration as part of our system testing procedures. It is
important that the system be re-initialized utilizing the SmartStart feature upon
installation. This will result in a customized default configuration.
The IF630 System will not recognize or communicate with any of the
connected devices until the SmartStart process has been exercised. The
IF630 will not report an alarm until this process has been completed. Refer
to the programming section of this manual for details about activating
SmartStart.
After the SmartStart routine has reinitialized the IF630, the system will be
configured as follows:
1.
All (input) initiating points are configured to be "Automatic" initiating points
(standard smoke detector points). Point Identification Devices (PID's) shall be
configured as manual stations if the priority interrupt is set.
2.
The system defaults to Security Level #2 (Acknowledge, Signal Silence and
Reset Switches are accessible without a password).
3.
Whenever any input point(s) goes into alarm:
A. All output signaling circuits activate and produce a steady, 24VDC output.
B. All output relays are activated.
C. The city-tie and common alarm relays activated.
____________________________________________________________________________________________
Normal Quiescent
Condition (default)
When the system is in the normal quiescent condition, the green "Power On" LED is
illuminated indicating the system is operating from normal AC line power. All
input and output circuits are "normal" (no alarm or trouble conditions). All other
LED's and alphanumeric display are extinguished, the system internal buzzer is
silent. To view system status message, press "
Enter
". Refer to Figure O-1.
In the normal condition, the green "Power-On" LED will be 'ON' - steady. All other
indicators will be extinguished.
ÛNOTE: The system is equipped with a built-in screen saver. When the system
remains in the idle mode (i.e. normal quiescent condition) for over 15 seconds the
screen will automatically go blank.
Status :Normal
MM/DD/YY HH:MM
System Idle
Figure O-1
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...