IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
71
Change Menu 4
Change Menu
1=Menu 1 2=Menu 2 3=Menu 3
4=Menu 4 0=Exit
>4
Change Menu 4
1=Cfg 2=Water 3=Relse 4=Dump
5=Dict 6=Card 0=Exit
Change Config
Changing the system configuration requires a previously downloaded system configuration
file. This option is only available when programming through a P. C. attached to the serial
port, or from the Master in a network.
WARNING: It is necessary to perform a Smart Start on the
panel before uploading a new configuration. Failure to do so
will result in unpredictable operation of the panel
Change Menu 4
1=Cfg 2=Water 3=Relse 4=Dump
5=Dict 6=Card 0=Exit
>1
[If network, upload will start at this point]
Ready to Upload Configuration File.
To
Upload:
1. Press PgUp
2. Choose 7 (ASCII)
3. Enter Filename
Change Water
Flow Delay
The Change Water option allows the selection of the delay time before a Water flow alarm
is activated..
Change Menu 4
1=Cfg 2=Water 3=Relse 4=Dump
5=Dict 6=Card 0=Exit
>2
Waterflow Zone Delay Is Set To: 30 sec
Enter Waterflow Delay (5-90 sec):
Change
Releasing Delay
The Change Relse option allows the selection of the time delay from the ANDed releasing
alarms to the Discharge command..
Change Menu 4
1=Cfg 2=Water 3=Relse 4=Dump
5=Dict 6=Card 0=Exit
>3
Releasing Delay Is Set To: 30 sec
Enter Releasing Delay (15-60 sec):
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...