IdentiFlex 630 Installation and Operation Manual
S
mart
S
tart Capable
9-25-96
10
OPERATING PROCEDURES
Acknowledging
the Alarm
Condition
When the user presses the "ACK" switch to acknowledge an alarm condition,
the following actions will occur.
1.
The control panel's internal audible buzzer will (always) silence.
2.
The acknowledge key's activation is logged into the History Buffer to
provide a time stamped record of the event's occurrence.
3.
The Acknowledge red LED will extinguish.
4.
Any outputs programmed to return to the normal condition upon pressing
the "ACK" switch will return to normal at this time.
5.
The red LED's for RESET and SIGNAL SILENCE switches will flash.
This "guided prompt" feature notifies the user that the next expected action
is to
Reset
the system or
Silence
the signals (if so programmed).
____________________________________________________________________________________________
Signal Silence
In the Alarm condition, the red LED for SIGNAL SILENCE will begin to flash.
This guided prompt feature notifies the user that it is possible, but not
necessary, to press the SIGNAL SILENCE switch. In the
default mode
, all
signal circuits will silence.
If the user presses the SIGNAL SILENCE switch, the following actions will
occur:
1.
The LED for the SIGNAL SILENCE switch will remain flashing.
2.
All output signal circuits which have been programmed to silence when the
SIGNAL SILENCE switch is activated (which is all output circuits in the
"default" case) will silence and the red activated LED will extinguish.
Resound or Return
of Signals
1. The signal silence switch is an alternating action switch. If the user
subsequently presses the SIGNAL SILENCE switch again, the signal
circuits will activate.
2. All the output signal circuits which had deactivated will reactivate;
returning to the
Alarm
condition. Tthe red active LED’s will light.
____________________________________________________________________________________________
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...