IF630
System Operation/Installation 5/26/01
___________________________________________________________________________________________
Rev 3.0
17
2. Remove the two horizontal cross rails.
3. Remove five main chassis mounting hex nuts. Remove the main chassis.
4. Secure the cabinet to the mounting foundation. Connect all conduit and
secure.
5. Ensure the cabinet is clean before re-mounting the main chassis. Clean as
required.
6. Mount the main chassis to the cabinet studs and secure hex nuts.
7.
Connect all field wiring. Referenced drawing D-W1145, Wiring, IF630
Analog Addressable System as required (or D-W1160 for IF630-126).. (All
field wiring must be in accordance with N.F.P.A. pamphlet #70 article #760.)
Ensure the cabinet is clean.
8. Mount the cross rails and secure.
9. Position the operators display into alignment pins of cross rails.
10. Plug in the battery charger card.
11. Re-mount the dead front panel and secure.