IdentiFlex 630 Installation and Operation Manual
S
mart
S
tart Capable
9-25-96
28
Analog Addressable Card
Circuit 1
Terminal #
Designation
Description
Lower
1
+24
+24 vdc
Terminal
2
+24 R
+24 vdc return
Block
3
L1
Common (-)
4
L1R
Common (-) return
5
L2
Data
6
L2R
Data return
Circuit 2
Terminal #
Designation
Description
Lower
7
+24
+24 vdc
Terminal
8
+24 R
+24 vdc return
Block
9
L1
Common (-)
10
L1R
Common (-) return
11
L2
Data
12
L2R
Data return
Circuit 3
Terminal #
Designation
Description
Upper
1
+24
+24 vdc
Terminal
2
+24 R
+24 vdc return
Block
3
L1
Common (-)
(optional)
4
L1R
Common (-) return
5
L2
Data
6
L2R
Data return
Circuit 4
Terminal #
Designation
Description
Upper
7
+24
+24 vdc
Terminal
8
+24 R
+24 vdc return
Block
9
L1
Common (-)
(optional)
10
L1R
Common (-) return
11
L2
Data
12
L2R
Data return
Analog Circuit Wiring Requirements and Limitations :
1.
Cable length per circuit - 4,000 feet maximum including all "T-tap' runs. “T-Tap” wiring is
not allowed on signal circuits.
2.
Use twisted cable wherever possible, even when in conduit.
3.
Twisted cable required on all open wiring runs involving 1,000 Ft. or more.
4.
Avoid running circuits parallel with power wiring for any distance.
5.
Avoid running circuits parallel with cables having high switching rates.
6.
Avoid running circuits parallel with fluorescent fixtures.
7.
Avoid running analog circuits parallel with signal circuit wiring.
8.
Shield signal circuit wiring, even if in conduit, if run together with analog circuits.
9.
Maximum conductor resistance for circuits is 25 ohms.
Table 4
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...