IF630
System Test Mode 5/26/01
___________________________________________________________________________________________
Rev 3.0
39
11. The system will now enter the Walk Test Mode. The Acknowledge and Trouble LED’s will
flash and the buzzer will sound. The system will remain in Trouble until all Walk Test
devices are cleared from the system.
Status: Fault
XX/XX/94 xx:xx
System in Walk Test
Figure T6
∆∆∆∆
WARNING !
If the system is in Walk Test mode ,and a device not in the test
mode is activated, the system will go into alarm and all output
circuits will be activated.
Once the system has been reset after an actual alarm all Walk
Test settings will be cleared.
12. To clear Walk Test operation each device and output must be individually taken out of Walk
Test. This is accomplished in the same manner as described in steps 1-10 above. Each
device must be set to “NOT IN WALK TEST”.
13. If all devices have been cleared from Walk Test the system will return to the Idle Mode.
____________________________________________________________________________________________
ByPass Mode
The ByPass function is used to remove an addressable device or signal circuit
from service. Bypassing a device will disable the control panel response from the
device selected or prevent activation of the device or signal circuit.
1.
From the Operational Mode menu, press key marked ‘ByPass’ keypad (default Access Level
3).
2.
Figure T7 is now displayed. The ByPass LED will flash at 120 PPM.
BYPASS MENU
1=DISPLAY 2=PROG
0=EXIT
Figure T7
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...