IdentiFlex 630 Installation and Operation Manual
S
mart
S
tart Capable
9-25-96
52
Û
NOTE: The cursor will be flashing under the circuit number.
If the device type is an ion detector Figure 8 will be displayed.
Ckt:XX Add:XXX D_Type: Ion Z_Type: XXXX
I
_GRP:XXX
Figure 8
Û
NOTE: The display starts with Circuit 1 and begins with the
highest address in circuit.
Field Descriptions
“Ckt”: xx"
Indicates the circuit (analog line or conventional) that has been
selected.
"Add: xxx"
Shows the address of the device to be modified (1 - 126).
"D_Type:xxx"
“Comp:x”
“Sens:x”
“R/R:x”
“FTemp:x”
Shows the type of device (from type code of addressed device). If
the device type is a photo detector, Figure 8A will be displayed. For
a complete list of Device Types refer to Table P3 - page 52.
A photo detector can be selected for operation with background
compensation (Yes) or without background compensation (no).
Default is Yes.
The sensitivity range of a photo detector can be adjusted
(compensated) to the environment. The device sensitivity range; 3
is the least sensitive and 0 is the most sensitive. The default is ‘2’.
If the device is a heat detector, Figure 8B will be displayed. If the
device is a heat detector, the rate of rise parameters can be defined in
Celsius or Fahrenheit.
"Z_Type: xxx"
Shows the type of zone that has been selected for the device. Zone
types are defined in Zone Type Table P2 - page 52.
"I_GRP: x"
Indicates the selected initiating group of the device. Each input
device can only be assigned to one group. One initiating group can
contain many input devices (logically arranged). The user can utilize
up to 256 initiating groups.
"W1:xxx "
Indicates the five (5) separate word dictionaries (W1 - W5) stored
and words contained in each dictionary (0 - 127 coded words). This
field is not displayed until selected. Refer to Table P4.
Û
NOTE: The user can scroll through field variables using
up/down arrow keys or enter the address number directly via
the key pad.
Device Selection
4.
Use the left/right arrow keys to move the cursor flashing under the device
address "Add:xxx", enter the address number or use the up/down arrow keys to
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...