IdentiFlex 630 Installation and Operation Manual
S
mart
S
tart Capable
9-25-96
58
Field Descriptions for Signal Circuits and Analog Addressable
“Ckt:xxx”
Indicates the signal circuits memory address
“Add:xxx
Address of analog relay module
“D_Type:Sig”
Shows the type of output circuit
“ALR:x”
Indicates to what alarm level the circuit will be activated
in the event that “and” zones are programmed.
NOTE: The use of Cross and Counting Zones must
comply with the applicable requirements of NFPA 72,
3-8.2.5:
Systems that require the operation of two automatic
detection devices to initialize the alarm response shall
be permitted, provided:
(a) They are not prohibited by the authority having jurisdiction.
(b) There are at least two automatic detection devices in each protected
space.
(c) Automatic detection device area spacing is no more
than one-half that determined by the application of
NFPA 72 Chapter 5.
“Sig:xxx”
Indicates the type of signaling to be output by the circuit
(i.e. steady, marchtime, etc). Refer to table P5
for
a complete description
.
“Res:xxx”
Indicates when the signal circuit has been programmed to
return to normal. See table P6 for a complete list of
options.
“DRL:x”
Indicates if a signal circuit will activate when the drill switch is depressed.
“Sil:x”
Auto Silence - 10 minutes.
“O_Grp:xxx”
Identifies the output group to be modified.
“Seq:”
Sequentially
Restores.
Û
NOTE: If an analog addressable line (or single device) is not
present when selected, the result is no action.
4. Program the signal circuit by using the left/right arrow keys to move between fields and the
up/down keys to assign the desired characteristics.
5. To program the second signal circuit press its associated switch and repeat step 4.
6. To exit output circuit programming press the “
Enter
” key.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...