IF630 Programming 5/26/01
___________________________________________________________________________________________
Rev 3.0
59
Signal Circuit Types
Output Signal
Circuit Type
A. STEADY DC
Steady DC type signal circuit is the System Default. When Activated, any
signal circuits programmed for Steady DC will provide a 24VDC
uninterrupted output.
B. MARCHTIME 60
Marchtime 60 circuits, when activated, will provide a 24 VDC output on the
selected circuits at a 60 pulses per minute rate with a duration of 50% on and
50% off cycle.
C. MARCHTIME 120
Marchtime 120 circuits, when activated, will provide a 24 VDC output on
the selected circuits at a 120 pulses per minute rate with a duration of 50%
on and 50% off cycle.
D. TEMPORAL
Temporal signaling circuits, when activated, will provide a 24 VDC output
in the pattern of a Morse Code "U". This pattern is active for .25 seconds,
off for .25 seconds, active for .25 seconds, off for .25 seconds, active for .75
seconds, off for .75 seconds. The pattern repeats until the circuit is returned
to Idle.
E. CALIFORNIA UNIFORM FIRE CODE
California Uniform Fire Code Signal circuits, when activated, will provide a
24 VDC output in Marchtime 120 format for 10 seconds on and 5 seconds
off. The pattern repeats until the circuit is returned to Idle.
F. CODED
Zone coded signaling circuits when activated will produce a 24VDC pulsed
numeric code to be transmitted up to 6 times or as programmed. A separate
code is usually transmitted for each input zone.
Signal Circuit
Restore
A. Restore On - ACKNOWLEDGE
Any active output point programmed to restore on ACKNOWLEDGE will
return to Idle whenever the Acknowledge switch is pressed. All output
points that were returned to Idle will reactivate upon a subsequent alarm.
B Restore On - SIGNAL SILENCE (** System Default **)
Any active output point programmed to restore on Signal Silence will be
silenced by the activation of the Signal Silence Switch and will return to Idle.
The Signal Silence Switch operates as a toggle switch. All outputs that were
returned to idle will reactivate upon a subsequent alarm or by depressing the
Signal Silence Switch again. Both Signal Circuits and Relay Outputs can be
programmed to restore on Signal Silence.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...