IdentiFlex 630 Installation and Operation Manual
S
mart
S
tart Capable
9-25-96
60
C. Restore On - RESET
Serves as System Default. Any active output point not programmed or de-
programmed from Restore on Acknowledge, or Restore on Signal Silence
will cause the output point to restore on RESET.
Û
NOTE: There are a few restrictions to be aware of regarding
output signal circuits:
1. The two signal circuits on the Bus Driver Module (BDM) can be
used for steady or pulsing DC (marchtime, temporal, etc.) and
programmed separately.
Alarm Levels
Available
There are three levels of alarm that can be assigned to each type of output
circuit, PreAlarm, 1st Alarm or 2nd Alarm. These levels designate at which
level of alarm an output circuit will activate. Output circuits assigned to 1st
alarm level (system default) will activate when a first alarm is detected on its
assigned input circuit(s), provided the input circuit is assigned to activate
that output circuit in the CBE table. Circuits designated as PreAlarm will
activate when a prealarm level is detected on an input circuit. Circuits
requiring activation on 2nd alarm (AND zones) can be assigned to alarm
level 2. An AND zone assigned to activate both 1st and 2nd alarm level
output circuits will activate only those outputs assigned to level 1 during a
first alarm condition. When a second alarm is detected both first and second
alarm outputs will activate. A shorting device will activate both first and
second alarm outputs (CZI).
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...