MPCe/LPCe Users Manual
26
Set Points Menu
The set point menu displays a list of all 8 available set points. From this menu, the mode, on point and off point
can be seen as well as a pull down menu for selecting the set point to be edited. Pressing edit will open the
respective edit set point parameters screen. When set points have been configured, press close to return to the
main menu.
Edit Set Point Parameters
The Mode determines if the set point is active and which supply it is dependant on. By default, all set points are
disabled.
The set point parameters are defined as:
•
On Point – This is the pressure that the set point relay will activate. The set point will activate when the
pressure is equal to or
lower than
this pressure.
•
Off Point – This is the pressure that the set point relay will deactivate. The set point will deactivate when
the pressure is equal to or
higher than
this pressure.
•
The off point must be equal to or greater pressure than the on point.