AL176 Circuit 1 – Overload compressor 2
M
Stop compr.2 Circ.1
No
AL178 Circuit 1 – Pump-Down end for maximum time
A
Stop circuit 1
Parameter
B035
AL200 Circuit 2 – Alarm discharge probe pressure
A
Stop circuit 2
10s
AL201 Circuit 2 – Alarm suction probe pressure
A
Stop circuit 2
10s
AL202 Circuit 2 – Alarm discharge probe temperature
A
Stop circuit 2
10s
AL203 Circuit 2 – Alarm suction probe temperature
A
Stop circuit 2
10s
AL205 Circuit 2 Envelope – High compression ratio
A
Stop circuit 2
Parameter
Cb17
AL206 Circuit 2 Envelope – High discharge pressure
M
Stop circuit 2
Parameter
Cb17
AL208 Circuit 2 Envelope – High suction pressure
A
Stop circuit 2
Parameter
Cb17
AL209 Circuit 2 Envelope – Low compression ratio
A
Stop circuit 2
Parameter
Cb17
AL210 Circuit 2 Envelope – Low differential pressure
A
Stop circuit 2
Parameter
Cb18
AL211 Circuit 2 Envelope – Low discharge pressure
A
Stop circuit 2
Parameter
Cb17
AL212 Circuit 2 Envelope – Low suction pressure
A
Stop circuit 2
Parameter
Cb17
AL213 Circuit 2 Envelope – High discharge temperature
A
Stop circuit 2
Parameter
Cb17
AL223 Circuit 2 EVD – Offline
A
Stop circuit 2
No
AL265 Circuit 2 – Alarm freeze evaporation
temperature
M
Stop circuit 2
Parameter
A041
AL266 Circuit 2 – Compressor 1 maintenance
A
None
Parameter
Ca00
AL267 Circuit 2 – Compressor 2 maintenance
A
None
Parameter
Ca02
AL273 Circuit 2 – High pressure alarm by pressure
switch
M
Stop circuit 2
No
AL274 Circuit 2 – Low pressure alarm by pressure
switch
R
Stop circuit 2
Parameter
Ca19/Ca20
AL275 Circuit 2 – Overload compressor 1
M
Stop compr.1 Circ.2
No
AL276 Circuit 2 – Overload compressor 2
M
Stop compr.2 Circ.2
No
AL278 Circuit 2 – Pump-Down end for maximum time
A
Stop circuit 2
Parameter
B035
Reset:
A: automatic reset
M: manual reset
R: Automatic reset with retries