Q.uick Start Guide
Q.brixx
67
Gantner Instruments Inc.
USA | China | Singapore | India | Austria | Germany | France | Sweden
1550 Hotel Circle N ∙ Suite 180 ∙ San Diego CA ∙ 92108 ∙ T +1 888 ∙ 512 ∙ 5788
info.us@gantner-instruments.com
www.gantner-instruments.com
Correct:
•
The 1
st
data buffer is the basic sample rate of the entire Q.station, therefore it
must obtain its synchronization source internally. Data buffers 2 to 4 can obtain
its synchronization internally or externally (i.e. angular synchronization).
•
It is possible to create up to 20 x separate data loggers within a single Q.station.
•
A single data logger can obtain data (i.e. channels/variables) from 1 x data
buffer.
•
The logging rate of a data logger can be the same or less than the data buffer it
is assigned to.
Sample Rate Assignment
1.
Configure the number of data buffers to create. Double-click on the Q.station
and navigate to Sample rate > Count. Enter the number of sample rates (1 to 4).