4-20mA Loop Fine Tune Adjustment

The current loop output is proportional to the elevator load including any attached chain (4mA when empty to 20mA when at capacity). 

Although the unit provides an accurate output without the need for any adjustment, this procedure offers a quick and simple means of 

measuring the output using a multi-meter connected in series with the 4-20mA Loop output terminals, and without having to monitor the 

sensor. The output can also be re-tuned during the process, if required. 

Connect the multi-meter as shown below:

Control

Signal

4-20mA

Loop

Do not connect the meter across the 4-20mA output.  

This may result in a blown fuse in your meter.

 

 

   

Cal

Load

Zero

Model EWS 102

Elevator Load Weighing Device

12-24VDC

1

2

3

ww

w

.garan.co.uk

+Exc

+Sig

-Sig

-Exc

Scn

Control

Signal

4-20mA

Loop

Power Supply

Common Ground

4-20mA Output to Elevator Drive Unit 

Controller/Driver Input

Operating Mode

Operating Mode

Fine Tune Procedure 

T

o enter the test and fine tuning p

rocedure, 

press the 

 button (unit beeps), hold it for 

about a second and then release it (unit beeps 

again).

To go straight to the Loop output test, press   

4mA output. At this point, the meter should measure 

4mA exactly. If necessary, press   to enable

 fin

e tuning 

or press   to move to the 20mA setting. To adjust 

the 4mA output, use the     and   buttons to edit 

the displayed 3-digit value. Once adjusted, save it by 

pressing  

 .

The meter should now measure 20mA exactly. If 

necessary, press   t

o enable fine tuning or p

ress   to 

exit test mode. To adjust the 20mA output, use the     

and   buttons to edit the displayed 4-digit value. Once 

adjusted, save it by pressing  

 .