PP610/612 LED lighting controllers - User Manual
E33
Unrecognised command or parameters.
E43
Illegal mode or channel number in command
Commands take effect immediately they are issued. Because of this, if the
settings are being changed from high current pulsed output mode to a
continuous output mode, it is advisable to set the current values to 0 using
the
RC
command before changing mode. This prevents overload
conditions occurring.
Note:
Any changes made using RS232 commands are not saved
permanently until the
AW
command has been issued.
10.1
General commands
Save the settings to memory
AW
Once the settings are saved to memory they are then retained when
the unit is switched off. If this is not done, changes to the settings are
volatile, and if the unit is switched off they revert to those in force
when the last
AW
command was issued.
Report the current settings for the outputs
ST
The first and second lines of the response report the output settings.
The format is either:
fMmEeVa,b,c,d
For constant or selected mode
Or:
fMmEeCaDdelPp
For pulsed output mode
Where:
f
output channel (1 or 2)
m
=
0 for continuous output
1 for trigger on Input 1
2 for trigger in Input 2
3 for trigger on both inputs
4 for select on Input 1
5 for select on Input 2
6 for select on both inputs
a
output current 1
b
output current 2
c
output current 3
—
39
—