13-18-612 Page 17
2-6
The appropriate installation and use of 75ºC wire is the responsibility of the electrical professional(s) performing the
installation and must be per NEC, local and state regulations as allowed. All of the above recommended minimum
wire sizes are based on all terminal connections being rated at 75ºC minimum temperature rating and copper wire
run lengths of 100 feet or less. Please note that all UL-508A listed control panels are rated for 40ºC ambient
conditions
Please refer to Section 6 of this manual for detailed instructions on the installation, operation and
maintenance of the water cooled heat exchangers.
ELECTRICAL WIRING -
The compressor package is (internally) factory wired for use with the voltage
specified on the order - it is only necessary to connect power supply and ground wires to the provided
wire terminal blocks.
Electrical shock can cause injury or death. Open main disconnect switch, lockout and
tagout before working on control box.
Gardner Denver Guidelines for proper wiring, grounding and feed power conditioning -
This
compressor package is provided with a variable speed drive (VFD) to control compressor motor. The
indicated Gardner Denver guidelines for proper wiring, grounding, and feed power conditioning must be
followed in order to protect the VFD electronics. Failure to do so will void your warranty.
Electrical Wire Sizing
– A certified electrician familiar with National Electric Codes and applicable local
codes shall size the electrical power wires serving the compressor package. Refer to Figure 2-2, for a
summary of maximum package current consumption values.
460 - 575 VOLT VS-80 and VS-110 MINIMUM COPPER SUPPLY WIRE RECOMMENDATIONS
460 Volt
APEX VS 80 through VS 110
Minimum Copper Supply Wire Recommendations
Model
Minimum Supply
Conductor
Ampacity
Minimum 75°C
Copper Wire
Sized @ 30°C
Minimum 75°C
Copper Wire
Sized @ 40°C
Minimum 75°C
Copper Wire
Sized @ 45°C
Notes
VS 80
202
4/0
4/0
250
VS 110
265
300 or 2/0 (2) 350 or 3/0 (2)
400 or 4/0 (2)
[1]
575 Volt
VS 80
123
1
1/0
1/0
VS 110
176
3/0
3/0
4/0
Notes: Wire sizes are per Table 310.15(B)(16) in the National Electrical Code (NEC)
[1]
2/0, 3/0, and 4/0 wires sized with derate for two parallel sets of conductors in a
single conduit. [2] Wires sized with derate for two parallel sets of conductors in a single
conduit.
[3]
Wires sized for two parallel sets of conductors in two conduits (one set in each conduit).
Figure 2- 2
– PACKAGE MAXIMUM CURRENT CONSUMPTION SUMMARY
Summary of Contents for AirSmart VS80-110B
Page 33: ...13 18 612 Page 32 4 7 300CGE546 04 Ref Drawing Page 2 of 4...
Page 34: ...13 18 612 Page 33 4 8 300CGE546 04 Ref Drawing Page 3 of 4...
Page 35: ...13 18 612 Page 34 4 9 300CGE546 04 Ref Drawing Page 4 of 4...
Page 37: ...13 18 612 Page 36 4 11 301CGE546 B Ref Drawing Page 2 of 4...
Page 38: ...13 18 612 Page 37 4 12 301CGE546 B Ref Drawing Page 3 of 4...
Page 39: ...13 18 612 Page 38 4 13 301CGE546 B Ref Drawing Page 4 of 4...
Page 41: ...13 18 612 Page 40 4 15 302CGE546 05 Ref Drawing Page 2 of 4...
Page 42: ...13 18 612 Page 41 4 16 302CGE546 05 Ref Drawing Page 3 of 4...
Page 43: ...13 18 612 Page 42 4 17 302CGE546 05 Ref Drawing Page 4 of 4...
Page 45: ...13 18 612 Page 44 4 19 303CGE546 B Ref Drawing Page 2 of 4...
Page 46: ...13 18 612 Page 45 4 20 303CGE546 B Ref Drawing Page 3 of 4...
Page 47: ...13 18 612 Page 46 4 21 303CGE546 B Ref Drawing Page 4 of 4...
Page 70: ...13 18 612 Page 69 9 2 Figure 9 1 MINIMUM DISCHARGE PRESSURE CHECK VALVE...
Page 86: ...NOTES...
Page 87: ...NOTES...