background image

 

13-21-608    Page 17 

Extreme Cold Weather Operation (Down To -10

°

F, -23

°

C) 

 
In addition to the above, the following should be provided: 
 
1. 

It will be necessary to provide shutters or to block off part of the cooler in some manner since the 
cooler is greatly oversized for operation in these low temperatures.  Since shutters are not provided 
as a factory option, blocking off a portion of the cooler with plywood should be satisfactory. 

 
2. 

Auto operation should not be used in extreme environments. 

 
3. 

Some means of providing heat during shutdown.  Start-up should be provided.  There are various 
methods to accomplish this, but since openings are not provided for sump heaters, the use of radiant 
heaters is recommended.  The heaters should be sized to provide at least a +10

°

 F (-12

°

 C) 

environment for coolers, motor and sump.  Figure 2-3, page 16, shows how these might be located 
in a typical installation and sizes required. 

 
Remember unsheltered (outside) installations should be avoided where possible.  Installation next to a 
heated building where enough heat can be used to keep the compressor room above freezing will save 
many complications in the operation and installation of the unit. 
 
Refer to Engineering Data Sheet 13-9-411, available from an authorized Gardner Denver distributor, for 
the advantages of using the heat recovered from rotary compressors.  This heat recovery could easily 
pay for an adequate shelter for the unit. 
 

AUXILIARY AIR RECEIVER

 - An auxiliary air receiver is not required if the piping system is large and 

provides sufficient storage capacity to prevent rapid cycling.  When used, an air receiver should be of 
adequate size, provided with a relief valve of proper setting, a pressure gauge and a means of draining 
condensate. 
 

MOISTURE SEPARATOR/TRAP

 - Since the unit is equipped with a built-in aftercooler, a combination 

moisture separator and trap is recommended but optional. 
 

CONTROL PIPING

 - Control piping is not necessary since the Rotary Screw compressor unit is factory 

wired and piped for the control system specified. 
 

INLET LINE

 - Where an inlet line is used between the air filter and the compressor, it must be thoroughly 

cleaned on the inside to prevent dirt or scale from entering the compressor.  

If welded construction is 

used, the line must be shot blasted and cleaned to remove welding scale.

  In either case, the inlet 

line must be coated internally by galvanizing or painting with a moisture and oil-proof sealing lacquer.  Up 
to ten (10) feet (3 meters) in length, the inlet line should be the full size of the inlet opening on the 
compressor.  If an extra-long line is necessary, the pipe size should be increased according to Inlet Line 
Length Chart, Figure 2-4. 
 
Accessibility for inlet air filter servicing must be considered when relocating the filters from the unit to a 
remote location. 
 

INLET LINE LENGTHS 

 

 

Length of Inlet Line 

Diameter of Pipe Size 

 

 

0 to 10 Feet (0 to 3 Meters) ................................

Same as Compressor Inlet Opening 

10 to 17 Feet (3 to 5 Meters) ................................

One Size Larger Than Inlet Opening 

17 to 38 Feet (5 to 11.5 Meters) ................................

Two Sizes Larger Than Inlet Opening 

Figure 2-4 – INLET LINE LENGTHS 

Summary of Contents for ELECTRA-SAVER

Page 1: ...NTROLLER DOMESTIC and INTERNATIONAL MODELS EAQ99W 125 150 and 200 HP 60 HZ EBQ99R 125 150 and 200 HP 60 HZ EAU99AB 200 HP 60 HZ EBU99H 200 HP 60 HZ EAQ99W 100 125 and 150 HP 50 HZ 75 93 112 KW EBQ99R...

Page 2: ...to simplify servicing your compressor Authorized distributor service technicians are factory trained and skilled in compressor maintenance and repair They are ready to respond and assist you by provid...

Page 3: ...mical operation and minimum downtime Boxed text formats are used within this manual to alert users of the following conditions Safety Labels are used within this manual and affixed to the appropriate...

Page 4: ...low level of risk which if not avoided MAY result in a minor or moderate injury Burn Hazard Hot surface PROHIBITION MANDATORY ACTION REQUIREMENTS Do not Operate Compressor with Guard Removed Do Not Li...

Page 5: ...r oil system until the unit is shut down and the air pressure has been relieved Electrical shock can and may be fatal Perform all wiring in accordance with the National Electrical Code NFPA 70 and any...

Page 6: ...ion 7 Coupling 69 Section 8 Maintenance Schedule 72 Section 9 Troubleshooting 74 This book covers the following models HP KW PSIG Model Parts List Controller Manual Comm Module Manual 125 150 200 HP 6...

Page 7: ...ing 54 High Temperature Operation 49 Inlet Line 17 Inlet Screen And Tube 67 Inlet Valve 33 Installation For Cold Weather Operation 16 Installation Section 2 13 Lifting Unit 13 Location 14 Air Cooled U...

Page 8: ...ction 9 Troubleshooting 73 Series Piping 21 Service Check List 71 Every 125 Hours Operation 71 Every Year 71 Motor Lubrication 71 Oil Separator 71 Service Check List Air Filter 71 Shuttle Valve 34 Sol...

Page 9: ...ssor Unloaded Constant Speed Mode 38 Figure 4 9 Control Schematic Compressor At Full Load Constant Speed Mode 39 Figure 4 10 Control Schematic Compressor Unloaded Low Demand Mode Or Auto Mode 40 Figur...

Page 10: ...ir is drawn into the cavity between the main rotor lobes and secondary rotor grooves A When the rotors pass the inlet port cutoff air is trapped in the interlobe cavity and flows axially with the mesh...

Page 11: ...is injected directly into the compression chamber to remove heat of compression seal internal clearances and lubricate the rotors TURN VALVE ELECTRA SAVER ONLY The turn valve is a rotary helical valve...

Page 12: ...13 21 608 Page 11 Figure 1 4 COMPRESSOR MOTOR SIDE Figure 1 5 COOLER RESERVOIR SIDE 200EDM797 A Ref Drawing...

Page 13: ...13 21 608 Page 12 Figure 1 6 AIR OIL FLOW DIAGRAM 202EDM797 Ref Drawing...

Page 14: ...may also be moved into location by rolling on bars Lift compressor package by base only Do not use other places such as motors compressors or discharge manifold piping as lifting points The eyebolts...

Page 15: ...ent on all air cooled units The air cooled unit with the standard enclosure requires sufficient flow Figure 2 2 for the compressor oil aftercooling system and for electric motor cooling Air is drawn i...

Page 16: ...lts and shims to provide uniform support for the base OIL RESERVOIR DRAIN The oil drain is piped from the bottom of the reservoir to the side of the frame This drain is approximately 4 50 inches 115 m...

Page 17: ...ust be made the precautions required will depend on the severity of the environment The following are general guidelines for outside installations Cold Weather Down To 10 F 12 C 1 Be sure all drains t...

Page 18: ...iliary air receiver is not required if the piping system is large and provides sufficient storage capacity to prevent rapid cycling When used an air receiver should be of adequate size provided with a...

Page 19: ...e severe injury or death Consult filtration specialists for additional filtration and treatment equipment to meet health and safety standards BLOWDOWN VALVE PIPING The blowdown valve is piped back int...

Page 20: ...25 HP EAQ99W 1 9 2 4 3 2 4 8 55 Less than 1 PSI for any flow rate shown in the table 125 HP EBQ99R 1 8 2 2 3 0 4 5 55 150 HP EAQ99W 2 3 2 9 3 9 5 8 55 150 HP EBQ99R 2 1 2 6 3 4 5 2 55 200 HP EAQ99W 2...

Reviews: