13-17-621 Page 134
controller was able to
recover.
C.117
Fault
Error on
machine
parameters
Machine parameters
have been corrupted.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.118
Fault
Error on the
Permanent
Variable Tasks
An error occurred on the
task that processes and
manages permanent
variables. Internal
software or hardware
issue.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.119
Warning
Snapshot Task
error
An error occurred when
attempting to take or
process a snapshot.
Attempt to take the snapshot again. If the problem
persists, export the logs from the controller and
contact Gardner Denver service.
C.120
Information
Data log
recording
completed
successfully
Informational. Log
recording was
successful.
No action needed
C.121
Warning
Data log
recording
interrupted and
aborted
Data log recording was
interrupted.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.122
Warning
Data log value
of a registered
process variable
has violated
limits
An error occurred with
the format of one of the
variables being logged.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.123
Information
Snapshot
recording
completed
successfully
Informational. Snapshot
recording process was
successful.
No action needed
C.124
Warning
Snapshot
recording
interrupted and
aborted
Snapshot recording was
interrupted.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.125
Warning
Snapshot value
of a registered
process variable
has violated
limits
An error occurred with
the format of one of the
variables being logged.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.126
Fault
Error on the EIP
variable Tasks
The Ethernet IP task has
encountered an issue.
If the problem persists, export the logs from the
controller and contact Gardner Denver service.
C.127
Warning
No EIP
connection
detected, check
network cables.
An Ethernet IP
connection cannot be
detected. Cables may be
disconnected or the
network is not configured
properly.
Check cables and network configuration. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
C.128
Warning
Firewall Setting
error
A misconfiguration of the
firewall has been
detected.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.129
Warning
Error on Profiler
configuration
task
An error was
encountered trying to set
up the software profiler.
Internal software issue or
the task was interrupted.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.