Figure 83: Max Power Loss Time
4.2.10 Unlimited Power Loss Time
When the
Unlimited Power Loss Time
is turned
On
the
Max Power Loss Time
setting will be disabled
and the controller will allow the machine to restart regardless of the duration of the power failure.
4.2.11 Auto Restart Enable
Auto Restart Enable
can be toggled
on
or
off
by pressing the button show below in Figure 84. When
auto
restart
is enabled and a power failure occurs, the controller will automatically return the machine to the
operating state it was in prior to the power failure. With this setting off the machine will need to be started
again manually. A power failure event will cause a warning to be entered in the alarm history when auto
restart is enabled but it will not be treated as a fault.
Figure 84: Auto Restart Enable
4.2.12 Dryer Pre-Run Time
The
Dryer Pre-Run Time
is the time, in minutes, the machine dryer or external dryer should run to reach
its optimal operating temperature before the compressor motor will be allowed to start. The
Dryer Pre-Run
Time
can be set by selecting the input box and entering the time on the keypad window. Refer below Figure
85 for reference.