4.2 Control
Table 31 below lists the settings available under the
Control
submenu of
Settings
.
Table 31: Control Setting
Control Settings
Setting
Settings Available
Short Description
Control
User can set and select the operating mode between Automatic,
Sequencing, Constant, and Low Demand. This changes the way
the controller runs the machine in order to provide air to the
customer
s’ system.
Primary pressure band values can be set and edited here. The
primary pressure band defines the default pressure set points of
the compressor
Secondary pressure band values can be set and edited here. The
secondary pressure band defines alternative pressure set points
that can be activated by a timer or control input.
Change how the Inlet Valve is controlled. On machines that have
inlet modulation this allows the mode to be set to load/unload or
modulation.
Remote Halt mode can be set between the available options of
Timer, Immediate and Disabled.
Enable or disable starting and stopping the machine under timer
control.
Restart Delay time sets the amount of time the controller will wait
before restarting after a power failure.
Enable or disable activating the secondary pressure band under
timer control.
Max Power Loss Time defines the maximum duration of a power
failure event that can still allow a restart.
Enable or disable automatic restart of the machine after a power
failure.
Dryer pre-run time defines a timer that will be used to activate a
dryer prior to starting the compressor.