13-8-621 Page 12
WARNING
Electrical shock can cause injury or death. Open main disconnect switch,
lockout and tagout before working on control box.
GROUNDING
- Equipment must be grounded in accordance with Section 250 of the National Electrical
Code.
WARNING
Failure to properly ground the compressor package could result in injury or
death. Install ground wiring in accordance with the National Electrical Code
and any applicable local codes.
MOTOR LUBRICATION
- Long time satisfactory operation of an electric motor depends in large measure
on proper lubrication of the bearings. The following charts show recommended grease qualities and
regreasing intervals for ball bearing motors. For additional information, refer to the motor manufacturer’s
instructions.
The following procedure should be used in regreasing:
1. Stop the unit.
2. Disconnect, lockout and tagout the unit from the power supply.
3. Remove the relief plug and free hole of hardened grease.
4. Wipe lubrication fitting clean and add grease with a hand-operated grease gun.
5. Leave the relief plug temporarily off. Reconnect unit and run for about 20 minutes to expel the
excess grease.
6. Stop the unit. Replace the relief plug.
7. Restart the unit.
WARNING
Rotating machinery can cause injury or death. Open main disconnect, lockout
and tagout power supply to starter before working on the electric motor.
Summary of Contents for INTEGRA EFC99A
Page 9: ...13 8 621 Page 2 Figure 1 2 COMPRESSOR ILLUSTRATION 302EFC797 A Ref Drawing...
Page 12: ...13 8 621 Page 5 DECALS 206EAQ077 212EAQ077 218EAQ077 211EAQ077 207EAQ077...
Page 13: ...13 8 621 Page 6 DECALS 216EAQ077 217EAQ077 222EAQ077 221EAQ077 208EAQ077...
Page 29: ...13 8 621 Page 22 4 3 WIRING DIAGRAM 300EFC546 B Ref Drawing Page 1 of 2...
Page 30: ...13 8 621 Page 23 300EFC546 B Ref Drawing Page 2 of 2...