L132 RS,
50Hz + 60Hz, air-cooled "A" + water-cooled
"W"
L132 RS,
Electric motor
IP55 (IE3) - IEC
60034-2-1 ECA Qualifying
Rated speed of drive motor
[rpm]
650 / 2980
Rated speed of fan motor
"A" [kW]
2.6 (50Hz) ; 6.6 (60Hz)
Rated speed of fan motor
"W" [kW]
0.37 (50Hz) ; 0.66 (60Hz)
Recommended cable cross-section (380 / 400 /
460V)
[mm
2
]
3 x 120 PE70 / 3 x 95
PE50 /3 x 95 PE50
Recommended fuse rating (time-delayed) (380 /
400 / 460V)
"A" [A]
"W" [A]
3 x 315 / 3 x 315 / 3 x 315
3 x 315 / 3 x 315 / 3 x 250
Cooling air volume flow
"A" [m
3
/
min]
273 (50Hz) ; 248 (60Hz)
Cooling air volume flow
"W" [m
3
/
min]
100
Cooling air outlet temperature above ambient
temperature
"A" [°C]
29 (50Hz) ; 30 (60Hz)
Residual pressure at ambient temperature
"A" [Pa]
130 / 90 [35 °C / 45 °C] (50Hz) ;
70 / 40 [35 °C / 45 °C] (60Hz)
Cooling water volume (ΔT = 12K)
"W" [l/min]
170 @ Δp = 2.1 bar
Cooling water inlet temperature
"W" [°C]
min. 5 / max. 35
Cooling water outlet temperature
"W" [°C]
max. 55
Cooling water pressure
"W" [bar]
max. 10
Cooling water connections
"W"
EN 10226-1 Rp 11/4 (DIN 2999-R 1 1/2)
Total oil quantity
[l]
63
Compressed air connection
EN 10226-1 R 2 1/2 (DIN 2999-R 2 1/2)
Weight
[kg]
"A" = 2655
"W" = 2479
Dimensions L x W x H
[mm]
2290 x 1327 x 2039
Chart 9-9: Technical data; L132 RS, 50Hz + 60Hz, air-cooled "A", water-cooled "W"
*)
Data measurement and specification as per ISO1217 fourth edition, Appendix C & E and under the following con-
ditions:
Air suction pressure: 1 bar a / 14.5 psia
Air suction temperature: 20°C / 68°F air humidity: 0% (dry)
**)
Measured in an open area as per ISO 2151, tolerance 3 dB(A).
At CompAir, our philosophy is to continually improve our products. We therefore reserve the right to alter technical
data without prior notice.
Summary of Contents for L110 10A V4