13-25-637 v02 Page 26
7.1
Cooling air volume/minimum cross
Fig. 9
1
Cool air intake
2
Cool air exhaust (Fan rotation counter-clockwise)
3
Control cabinet cool air intake (L30RS-L45RS only)
The cooling air volume required by these screw
compressors is as follows:
L30
2296 cfm
L30RS
2296 cfm
L37
2755 cfm
L37RS
2755 cfm
L45
3073 cfm
L45RS
3073 cfm
If conditions are not favorable, we recommend the
installation of venting ducts. However, the velocity
of the cooling air should not exceed 17ft/sec. We
recommend a minimum duct cross-section of
approx. 6 ft
2
.
The figures below show the recommended
ventilation sections arrangement:
Fig. 10