19
TROUBLE SHOOTING GUIDE
SYMPTOM / FAULT
POSSIBLE CAUSES
CORRECTIVE ACTION
Low refrigerant head
pressure
Compressor flooding
System Noises
Compressor will not
unload
Compressor will not load
Rapid Unloader Cycling
Cold Compressor
(Cylinders and Crankcase
Sweating
Low Crankcase Oil Level
High Crankcase Tempera-
ture (should be 100
°
F/38
°
C
to 130
°
F/55
°
C at seal
housing).
1. Water-cooled units - Excessive water flow
Adjust water regulating valve.
through condenser
2. Suction shutoff valve partially closed
Open valve.
3. Leaky compressor suction valves
Examine valve discs and valve seats;
replace if necessary.
4. Worn piston rings
Replace if worn.
1. Defective or improperly set expansion
Reset to 3
°
F/1.7
°
C superheat.
valve
2. Defective or improperly set liquid
Reset to 65
°
F/18.3
°
C return gas
injection valve
temperature.
1. lnsufficient clearance between piston and
Replace defective parts.
valve plate
2. Unit foundation improperly isolated
Isolate foundation.
3. Improper support or isolation of piping
Use correct piping techniques, and
support piping with suitable hangers.
4. Slugging due to refrigerant feed back
Check expansion valve setting; check
sensor bulb for looseness and correct
location.
5. Piping vibration
Support pipes as required, check pipe
connections.
6. Hissing (insufficient refrigerant flow thru
Reclaim refrigerant, replace strainer,
expansion valves or clogged liquid line
and recharge with the proper amount of
strainer)
refrigerant.
7. Hot gas by-pass valve chattering
The chattering noise is normal and
does not affect the operation of the unit.
1. Capacity control valve inoperative
Repair.
2. Unloader solenoid stuck
Repair.
3. Unloader solenoid coil defective
Replace.
4. Hot gas by-pass valve set too high or
Reset or repair.
sticking
1. Capacity control valve stuck open
Repair or replace.
2. Unloader solenoid stuck
Repair.
3. Foaming in crankcase due to refrigerant
Check expansion valve, and piping.
flooding
1. Excessive fluctuation in suction pressure
Repair expansion valve.
2. System load fluctuating
Stabilize load.
1. Liquid carry-over from evaporator
Check refrigerant charge, expansion
valve, and desuperheating valve.
1. Oil return screen clogged
Clean.
2. Freon leak
Repair leak.
1. Desuperheating valve is out of adjustment
Check operation and adjust.
2. Liquid line strainer clogged
Clean.
3. Excessive superheat
Reset expansion valve.
4. Discharge temperature of 275
°
F/135
°
C
Check unit application.
5. Leaking suction or discharge valves
Replace.
6. Defective liquid injection valve.
Repair.
Summary of Contents for RHC Series
Page 9: ...9 Typical Wiring Schematic...