INSTALLATION

1.  Damage Check: check carton or crate for possible 

damage incurred in shipping. After carefully uncrating, 

check for “concealed” damage. Report any damage 

immediately to your carrier.

2.  The correct type of gas for which the unit was 

manufactured is noted on the rating plate, and this type 

of gas must be used.

3.  The gas pressure must be checked when the unit is 

installed, to ensure that the unit gas pressure is the same 

as specified on the rating plate. If necessary pressure 

adjustments can be made at the pressure regulator, 

supplied on each unit.

4.  Have a qualified gas technician check the gas pressure 

to make certain that existing gas facilities (meter, piping, 

etc.) will deliver the BTU’s of gas required at the unit with 

no more than ½” water column pressure drop. When 

checking pressure, be certain that all the equipment on 

same gas line is turned to the “ON” position.

5.  Make certain that the new piping, joints and connections 

have been made in a clean manner and have been 

purged, so that the piping compound, chips, etc will not 

clog pilots, valves and / or controls. Use pipe joint sealant 

that is certified for use with LP gas.

6. 

WARNING

;  check gas connections for leaks, using soap 

solution or similar means. DO NOT CHECK WITH AN OPEN 

FLAME.

Rating Plate 

All burner-input ratings are shown on the serial plate located 

on the right side panel of the appliance.

When corresponding with the factory or your local 

authorized factory service center regarding service problems 

or replacement parts, be sure to refer to the particular unit 

by the correct model number (including the prefix and suffix 

letters and numbers) and the warranty serial number. The 

rating plate affixed to the unit contains this information.

We suggest installation, maintenance and repairs should be 

performed by your local authorized service agency listed in 

your information manual pamphlet.

In the event you have any questions concerning the 

installation, use, care or service of the product, write or call 

our Product Service Department.

This product must be installed by professional personnel as 

specified. Garland products are not approved or authorized 

for home or residential use, but are intended for commercial 

applications only. Garland will not provide service, 

warranty, maintenance or support of any kind other than in 

commercial applications.

Gas Connections

The inlet manifold size for connection to the main gas supply 

is (1) 3/4”NPT inlet for each deck.

The importance of proper installation of Commercial 

Gas Cooking Equipment cannot be over-stressed. Proper 

performance of the equipment is dependent, in great part, 

on the compliance of the installation with the manufacturer’s 

specifications. Installation must conform to local codes 

and with the National Fuel Gas Code NFPA 54/ANSI Z223.1, 

Natural Gas Installation Code CAN/CGA-B149.1, or the 

Propane Installation Code CAN/CGA-B149.2, as applicable, 

including:

1.  The appliance and its individual shut-off valve must be 

disconnected from the gas supply piping system during 

any pressure testing of that system at test pressures in 

excess of 1/2 psi (3.45 kPa).

2.  The appliance must be isolated from the gas supply 

piping system by closing its individual manual shut-off 

valve during any pressure testing of the gas supply piping 

system at test pressures equal to or less than 1/2 psi (3.45 

kPa)

Before assembly and making gas connections, check gas 

supply.

A.  The type of gas for which the unit is equipped is stamped 

on the data plate located behind lower front panel. 

Connect a unit stamped “NAT” only to natural gas; 

connect those stamped “PRO” only to propane gas.

B.  If it is a new installation, have gas authorities check meter 

size and piping to assure that the unit is supplied with a 

sufficient amount of gas pressure to operate the unit.

C.  If it is additional or replacement equipment, have gas 

authorities check pressure to make certain that existing 

meter and piping will supply fuel at the unit with not 

more than ½” water column pressure drop.

NOTE: When checking pressure be sure that all other 

equipment on the same gas line is on. A pressure regulator is 

supplied with GARLAND Pizza Ovens. The regulator is preset 

to deliver gas at the pressure shown on the rating plate.

Summary of Contents for GPD Series

Page 1: ...FETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAU...

Page 2: ...roduct could expose you to air borne particles of glass wool ceramic fibers Inhalation of airborne particles of glass wool ceramic fibers is known to the State of California to cause cancer Operation...

Page 3: ...lling Under Ventilation Canopy 6 Installing with Direct Ventilation 6 ASSEMBLY INSTRUCTIONS 7 Leg Installation 7 Hearth Installation 7 Double Deck Assembly 8 Gas Connection 8 ADJUSTMENTS 5 Gas Pressur...

Page 4: ...ATIONS GPD SERIES Ratings shown are for natural gas installations up to 2000 feet 610m above sea level BTU input ratings must be de rated for high altitude installations Specify altitude of product if...

Page 5: ...ll our Product Service Department This product must be installed by professional personnel as specified Garland products are not approved or authorized for home or residential use but are intended for...

Page 6: ...e a subnormal atmospheric pressure will occur affecting the appliance operation adversely and causing undesirable working conditions 2 Appliances shall be located so as not to interfere with proper ci...

Page 7: ...TIONS Leg Installation On single deck units tip oven section units back On double deck units tip lower oven section ONLY on its back Each leg is secured with four 3 8 16mm hex head bolts threaded into...

Page 8: ...to the action of liquified petroleum gases 4 Each oven is supplied with two possible gas connection locations One is located on the right side and the other is located on the right rear corner 5 The r...

Page 9: ...y to check the gas supply B Dirty burner orifice or ports With the oven cold use a thin wire to check that the spud orifice nozzle is clear If necessary loosen and remove the spud Be careful when clea...

Page 10: ...the two loosened calibration lock screws being in contact with the ends of the screw clearance plate to the proper location reassemble screws in the other tapped holes designed for them NOTE NO ATTEM...

Page 11: ...f pilot does not continue to burn after releasing gas cock repeat steps 2 thru 5 or have a qualified serviceman check the system Do not allow anyone else to attempt repairs 7 Once pilot is lit turn ga...

Page 12: ...too long Reduce bake time By pass flame high Reduce by pass flame Thermostat Check actual temperature call for service Color overall light Short bake time Bake longer Lower temperature Increase temper...

Page 13: ...Document G_GO_OM_PYRODECK_4606131 12 20 Page 13 Notes...

Page 14: ...Document G_GO_OM_PYRODECK_4606131 12 20 Page 14 Notes...

Page 15: ...Document G_GO_OM_PYRODECK_4606131 12 20 Page 15 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 16: ...nvotherm Crem Delfield fitkitchen Frymaster Garland Kolpak Lincoln Manitowoc Merco Merrychef and Multiplex Bringing innovation to the table welbilt com 2020 Welbilt Inc except where explicitly stated...

Page 17: ...veland Convotherm Crem Delfield fitkitchen Frymaster Garland Kolpak Lincoln Manitowoc Merco Merrychef et Multiplex L innovation au service de la restauration welbilt com 2020 Welbilt Inc sauf indicati...

Page 18: ...Num ro du document G_GO_OM_PYRODECK_4606131 12 2020 Page 15 PAGE INTENTIONNELLEMENT LAISS E EN BLANC...

Page 19: ...Num ro du document G_GO_OM_PYRODECK_4606131 12 2020 Page 14 Remarques...

Page 20: ...Num ro du document G_GO_OM_PYRODECK_4606131 12 2020 Page 13 Remarques...

Page 21: ...n Thermostat V rifiez la temp rature r elle du four ou faites appel un professionnel Aliment trop clair Temps de cuisson trop court Augmentez le temps de cuisson Diminuez la temp rature du four Augmen...

Page 22: ...me par un r parateur qualifi Ne laissez personne d autre effectuer des r parations 7 Une fois le br leur de veille allum ouvrez le robinet de gaz Il est inutile de recommencer la proc dure d allumage...

Page 23: ...dure d talonnage susmentionn e car les deux vis de blocage d talonnage desserr es sont en contact avec les extr mit s de la plaque de d gagement vissez les dans les autres orifices taraud s con us cet...

Page 24: ...cteur gicleur n est pas obstru Si besoin est desserrez et retirez l injecteur Veillez ne pas agrandir l orifice de l injecteur lorsque vous le nettoyez Ensuite l aide d un fil ou d un clou fin retirez...

Page 25: ...reil et l autre sur le coin arri re droit de celui ci 5 Le raccord du c t droit est obstru l aide d un bouchon t te frais e de 3 4 Si vous utilisez ce raccord bouchez le raccord arri re 6 Le r gulateu...

Page 26: ...Min 3 Pieds 90cm Min INSTRUCTIONS D ASSEMBLAGE Installation des pieds Si l appareil est dot d un seul pont basculez le en arri re S il est double posez UNIQUEMENT la section inf rieure sur sa partie...

Page 27: ...les 2 Si l quipement est plac dans un espace confin il doit tre plac de sorte ne pas entraver la circulation de l air Tous les br leurs y compris les br leurs de veille ont besoin d assez d air pour f...

Page 28: ...duit doit tre install par un professionnel selon les instructions du pr sent manuel L utilisation domestique de produits Garland n est pas autoris e ni admise elle doit tre strictement commerciale Le...

Page 29: ...10 Po CE 25mbar SP CIFICATIONS D ENTR E Gaz Naturel Ou Propane MOD LE BTU HR KW Entr e Gaz GPD48 96 000 28 1 3 4 Po N P T GPD60 122 000 35 7 3 4 Po N P T GPD48 2 192 000 56 2 1Po N P T GPD60 2 244 000...

Page 30: ...une hotte 6 Installation avec un syst me de ventilation directe 6 INSTRUCTIONS D ASSEMBLAGE 7 Installation des pieds 7 Pose des soles 7 Assemblage de deux ponts 8 Raccordement de l arriv e de gaz 8 R...

Page 31: ...de laine de verre ou de fibres c ramiques en suspension dans l air L inhalation de particules de laine de verre ou de fibres c ramiques en suspension dans l air est reconnue par l tat de Californie c...

Page 32: ...CURIT NE STOCKEZ NI N UTILISEZ D ESSENCE OU AUTRES VAPEURS OU LIQUIDES INFLAMMABLES PROXIMIT DE TOUT APPAREIL AVERTISSEMENT L INSTALLATION LE R GLAGE L ALT RATION L ENTRETIEN OU LA MAINTENANCE INCORR...

Reviews: