Magnum 6KM Mobile Ethernet Switch Installation and User Guide
07/10
37
www GarrettCom com
.
.
NOTE: The GND should be hooked up first. The 6KM unit has a floating ground, so
the user may elect to Ground either + or - terminal to suit the customer’s use.
Before connecting live power lines to the input connector of –48VDC,
12VDC, 24VDC, 110VDC, 125VDC or 250VDC products, always use a digital
voltmeter to measure the output voltage of the power supply and determine the lead
which is more “+ve potential”. The more “+ve” voltage lead from 48V or –48V
supply must be connected to the post labeled “+”.
After confirmation of the output voltage:
1.
Turn off power to the supply line.
2.
Connect
supply
line to the unit.
3.
Apply power to the supply line.
4.
Confirm that the PWR led is illuminated.
B4.0
UL Requirements for DC-powered units
CAUTION: 48VDC products shall be installed with a readily accessible disconnect
device in the building installation supply circuit to the product.
Minimum 18AWG cable for connection to a Centralized DC power source.
1.
Minimum 14AWG cable for connection to an earth wiring.
2.
Use only with Listed 10A circuit breaker provided in building installation.
3.
“Complies with FDA radiation performance standards, 21 CFR subchapter J.”
or equivalent.
4.
To secure a centralized DC Power Source cable , use at least four cable ties to
secure the cable to the rack at least 4 inches apart, with the first one located
within 6 inches of the input connector.
B5.0 TROUBLESHOOTING
Please refer to Section 6.0 for troubleshooting