Page 7-50
MDE-4334C Atlas Start-up and Service Manual · April 2008
Hydraulic/Mechanical Components
Pumping Unit
6
Thread the cable from the reel through the cable grommet, and then through the hose clamp
lock ring.
7
Tie a knot and insert into the cable end.
8
Slide the cable end into the hose clamp lock ring. One-inch hoses use metal clamps instead of
plastic hose clamps.
9
Install a retriever clamp at the top of the loop. Attach a hose clamp lock ring (cable end) to the
hose clamp. Use a cap screw and hex head nut to secure. Do not overtighten. Always use
appropriately-sized, padded or contoured plastic clamps for hoses. Under-sized clamps will
damage the hose cover.
Figure 7-24: Replacing Retriever Reels, Cables and Hose Clamps
10
With the retriever cable fully extended, ensure that there is some slack on the hose. Do not
allow coaxial hoses to touch the ground when retracted and hanging.
Pumping Unit
GPU Pumping Unit
• Wear eye protection. Residual pressure and entrapped fuel may still be present
and may drain or spray while removing parts.
• Fire and explosion could result in severe injury or death.
• Shut off power to the unit.
• Remove parts slowly. Collect fuel in approved containers.
• Clean up all spills promptly.
WARNING