Page 7-68
MDE-4334C Atlas Start-up and Service Manual · April 2008
Hydraulic/Mechanical Components
Valves
Solenoid Valve and Filter Manifold
• Wear eye protection. Residual pressure and entrapped fuel may still be present
and may drain or spray while removing parts.
• Fire and explosion could result in severe injury or death.
• Test and close the shear valves involved. Shut off power to the unit.
• Remove parts slowly. Collect fuel in approved containers.
• Clean up all spills promptly.
WARNING
About Valve and Filter Manifolds
The Valve and Filter manifold connects to the meter inlet and provides filtration upstream of a
built-in 1” 2-stage solenoid valve. Filters should be selected and changed as per the section
. The valve diaphragm and coil are the serviceable parts. Use
Gasboy recommended kits for valve repair. Follow the instructions provided with the kit.
Recommended Solenoid Valve Repair Kits
Kit Description
Kit No.
ASCO Diaphragm Repair Kit
M04607K010
ASCO Coil Replacement Kit - 110/120V
M04607K012
ASCO Coil Replacement Kit - 220/240V
M04607K013
The manifold also provides probe and thermowell ports for the ATC option.