Select fuses, motor protective switches or thermal
protective switches to provide protection.  Fuses act as
short circuit protection for the motor, not as protection
against overload.  Incoming line fuses must be able to
withstand the motor’s starting current.  Motor starters
with thermal magnetic overload or circuit breakers
protect motor from overload or reduced voltage
conditions.  Motors without automatic restart require
thermal protection or magnetic over-current cutout to
prevent motor overloading from one phase in a 3-phase
circuit, high starting frequency or jammed blower.

The power required will rise as differential pressure
increases.  The wiring diagram attached to the product
or on page 6 of this manual provides required electrical
information.  Large motors have two diagrams, one for
50Hz wiring specifications and the other for 60Hz wiring
specifications.  Check that the power source is correct
to properly operate the dual-voltage motor.  If additional
information is required, please consult your Gast
Distributor/Representative.

Model with a power supply cord:

This product must be grounded.  For either 120-volt or
220/240-volt circuits connect power supply cord
grounding plug to a matching grounded outlet.  

Do not

use an adapter.

(See DIAGRAM A)

Model that is permanently wired:

This product must be connected to a grounded,
metallic, permanent wiring system, or an equipment
grounding terminal or lead on the product.

Power supply wiring must conform to all required safety
codes and be installed by a qualified person.  Check
that supply voltage agrees with that listed on product
nameplate.

Extension cords:

Use only a 3-wire extension cord that has a 3-blade
grounding plug.  Connect extension cord plug to a
matching 3-slot receptacle.  

Do not use an adapter.

Make sure your extension cord is in good condition.
Check that the gage wire of the extension cord is the
correct size wire to carry the current this product will
draw.

An undersized cord is a potential fire hazard, and will
cause a drop in line voltage resulting in loss of power
causing the product to overheat.  The following table
indicates the correct size cord for length required and
the ampere rating listed on the product nameplate.  

If in

doubt, use the next heavier gage cord.  The smaller
the gage number, the heavier the wire gage.

Check with a qualified electrician or serviceman if
the grounding instructions are not completely
understood, or if you are not sure whether the
product is properly grounded.  Do not modify the
plug provided.  If it will not fit the outlet, have the
proper outlet installed by a qualified electrician.

In the event of an electrical short circuit, grounding
reduces the risk of electric shock by providing an
escape wire for the electric current.  This product may
be equipped with a power supply cord having a
grounding wire with an appropriate grounding plug.
The plug must be plugged into an outlet that is properly
installed and grounded in accordance with all local
codes and ordinances.

Electrical Connection

Minimum gage for extension cords

Amps

Volts

Length of cord in feet

120v

25

50

100

150

200

250

300

400

500  

240v

50

100

200

300

400

500

600

800

1000

0-2

18

18

18

16

16

14

14

12

12

2-3

18

18

16

14

14

12

12

10

10

3-4

18

18

16

14

12

12

10

10

8

4-5

18

18

14

12

12

10

10

8

8

5-6

18

16

14

12

10

10

8

8

8

6-8

18

16

12

10

10

8

6

6

6

8-10

18

14

12

10

8

8

6

6

4

10-12

16

14

10

8

8

6

6

4

4

12-14

16

12

10

8

6

6

6

4

2

14-16

16

12

10

8

6

6

4

4

2

16-18

14

12

8

8

6

4

4

2

2

18-20

14

12

8

6

6

4

4

2

2

3

70-6000 REV J.qxd  7/23/07  2:54 PM  Page 3

Summary of Contents for R2303A

Page 1: ...R6P350A Shown Model R7P Shown Product Use Criteria Pump only clean dry air Operate at 20ºF 104ºF 29ºC 40ºC Protect unit from dirt moisture Do not pump flammable or explosive gases or use in an atmosphere that contains such gases Protect all surrounding items from exhaust air This exhaust air can become very hot Corrosive gases and particulate material will damage unit Water vapor oil based contami...

Page 2: ...install check valves that close with a strong spring The recommended check valves page 7 provide minimal pressure drop positive sealing and are resistant to the high discharge temperatures of large blowers WARNING DANGER Plumbing Remove any foreign material burrs chips welding drops slag pipe cuttings excess sealant sand or lime from plumbing Check motor mounting and rotation before connecting to ...

Page 3: ...d that has a 3 blade grounding plug Connect extension cord plug to a matching 3 slot receptacle Do not use an adapter Make sure your extension cord is in good condition Check that the gage wire of the extension cord is the correct size wire to carry the current this product will draw An undersized cord is a potential fire hazard and will cause a drop in line voltage resulting in loss of power caus...

Page 4: ...urning in the proper direction MAINTENANCE It is your responsibility to regularly inspect and make necessary repairs to this product in order to maintain proper operation Make sure that pressure and vacuum is released from product before starting maintenance Check filter elements and noise absorbing foam used in mufflers and clean motor and blower after first 500 hours of operation Replace filter ...

Page 5: ...ther as a result of breach of warranty negligence or otherwise Notwithstanding any other provision of this warranty BUYER S REMEDY AGAINST GAST FOR GOODS SUPPLIED OR FOR NON DELIVERED GOODS OR FAILURE TO FURNISH GOODS WHETHER OR NOT BASED ON NEGLIGENCE STRICT LIABILITY OR BREACH OF EXPRESS OR IMPLIED WARRANTY IS LIMITED SOLELY AT GAST S OPTION TO REPLACEMENT OF OR CURE OF SUCH NONCONFORMING OR NON...

Page 6: ... High Voltage Low Voltage High Voltage T14 T15 T16 T4 T5 T6 T7 T8 T9 T1 T2 T3 To reverse rotation on any 3 Phase motor interchange any two external motor line connections to any two line leads Models R2303A R3305A 1 R3305A 13 R4310A 2 R4P315A R6350A 2 R6P350A R6PP3110M R6PS3110M R7100A 3 R7P3180M R7S3180M R93150A Connections for 3 Phase 12 Leads Models R6335A 2 R6P335A Models R5325A 2 R6325A 2 BEF...

Page 7: ...5 SDR4 R6 R6P SDR6P R7 R7S SDR4 R4P SDR6 R6PS Part Number AH326B AH326C AH326D AH326F AH326G Dimension A 3 57 4 19 4 50 5 25 8 00 Dimension B 2 32 2 69 2 94 3 82 5 07 Dimension C 1 00 NPT 1 25 NPT 1 50 NPT 2 00 NPT 2 50 NPT MOISTURE SEPARATOR FOR VACUUM This moisture separator removes liquids from the gas stream in a vacuum process This helps protect the blower from corrosion and the build up of m...

Page 8: ...odel Number R1 R2 R3 R4 SDR4 R4P SDR5 SDR6 R6 R6PP SDR6P R7S R9 R4H R5 R6P R7M R6PS R7 R7S R9P R9S Part Number AJ151A AJ151B AJ151C AJ151D AJ151E AJ151G AJ151H AJ151M Dimension A 5 88 7 38 7 38 7 38 8 75 8 75 14 00 18 50 Dimension A1 16 25 20 75 Dimension B 4 50 6 81 6 81 6 81 10 25 10 50 27 13 28 13 Dimension C 2 75 4 62 4 62 4 62 5 00 5 50 18 50 19 50 Dimension D 1 00 FPT 1 00 FPT 1 25 FPT 1 50 ...

Page 9: ...blowers are drip proof when mounted as shown MPT Male Pipe Thread FPT Female Pipe Thread MUFFLERS Designed to reduce noise by up to 5 dbA and remove high frequency sound associated with all blowers 9 PARTS ORDERING INFORMATION REF ITEM QTY R1102 R2103 R2105 R2305B R3105 1 R1102C R2303A R3305A 1 R1102K R3305B 1 1 COVER 1 AJ101A AJ101B AJ101B AJ101B AJ101C 2 LOCK NUT 1 BC187 BC187 BC181 BC181 BC181 ...

Page 10: ...BB750 2 BB750 2 BB750 BB750 3 IMPELLER 1 AJ102K AJ102KA 2 AJ102KA 2 AJ102GZ AJ102GA 4 SQUARE KEY 1 AB136 AB136 2 AB136 2 AC628 AC628 5 SHIM SPACER AJ109 AJ169F AJ169F AJ110 AJ110 6 RETAINING RING 1 7 HOUSING 1 AJ103K AJ103KD 2 AJ103KD 2 AJ103GA AJ103GA 8 MUFFLER BOX 1 AJ104K AJ104GA AJ104GA 8A SCREEN 2 AJ998G AJ998G 9 SPRING 2 AJ113FQ 10A FOAM AJ112K 8 AJ112GA 8 AJ112GA 8 10B FOAM 2 11 MUFFLER EXT...

Page 11: ...EXPLODED PRODUCT VIEW 11 ...

Page 12: ...y Operating at too high a pressure or Install a relief valve and pressure or vacuum vacuum gauge Unusual sound Impeller is damaged or dirty Clean or replace impeller Bearing going bad Send unit to a Gast Authorized Service Facility Motor overload Low voltage Check power source Check wire size and wire connections Unit does not start Incorrect electrical connection or Check wiring diagram circuit f...

Reviews: