BAYKAN ISI SIST.SAN.TIC.AS
.
- 10 -
2. PLACEMENT OF THE WALL HUNG BOILER
2.1 MOUNTING THE WALL HUNG BOILER
TO THE WALL
Considering the dimensions of your device
and by using the installing and mounting
diagram on the packages, determine the
positions of wall screws and sign them.
NOTE: You should leave a space of at least
40 cm. under the device while mounting
your boiler to the wall.
Determine the positions of connecting
parts by using the assembly figure.. Fig.6
Place the hanging screws in their positions
according to the measurements given in
the figure.
Hang your wall hung boiler to hanging
screws.
2.2 WATER AND GAS CONNECTIONS
Before starting the procedures related with water
connections, we recommend you to wash the
installation in order to get rid of the particles that may
be present in pipes and radiators.
Connect
the
water
and
gas
according
to
the positions shown in the figure.
Connect the outlet of safety valve to the
waste water line by means of a hose.
(Otherwise, the manufacturer of the wall hung
boiler shall not be liable for the cases that arise
due to the intermeddling of the safety valve. )
Place a valve to the inlet of each of water
and gas pipe lines.
Ensure that the pressure of domestic
water is 1-6 bars. If the water pressure is
higher than 6 bars, use pressure set up
valve.
A dirt collector must be connected to the
water entries.
fi
ek.6
Perform the followings for a good gas connection.
Ensure that the Gas pipe is clean, clean around it.
The building internal gas distribution pipe must conform to the technical specifications and
regulations.
An
elastic
connection
between
the device and internal gas line of the building must be
made. (3/4”).
The proper sealed and hermetic gaskets must be used for spacing connection.
Inspect and compare the gas inlet pressure values and the gas inlet values of the building.
These adjustments are only performed by Baykan Service Headquarters and Baykan
authorized personnel.
Do not forget to let the air in the gas pipe out.
NOTE: When the conversion from natural gas to L.P.G. is being performed, the burner jets
suitable for L.P.G. must be changed. The gas inlet pressure should not exceed 60mbars.