F-Guard IR3 H2 HD User Manual
9
Specifications
Fire Detection
•
Detection time and distance:
o
40ms
-
for fast fire burst or explosion
o
1.5s
-
for
32″ (0.8m) hydrogen fire at 0
–66ft. (0–20m)
o
4s
-
for
32″ (0.8m) hydrogen fire at 66
–100ft. (20–30m)
o
Field of view: 90° Horizontal, 75° Vertical
o
Time Delay: 0-30 seconds (adjustable)
o
Built-in test: Automatic and Manual
Video Functionality
o
Near IR camera provides a live greyscale video feed.
o
If RGB camera option selected, HD Video allowing clear imaging of fire and people at 100ft.
(30m) distance.
o
Video recording of alarm events 1 minute before and up to 3 minutes after the flame is
detected.
o
System integration protocol: ONVIF (Open Network Video Interface Forum) Profile S
Electrical Specifications
o
Operating Voltage: 24 VDC nominal (18-32 VDC)
o
Current Consumption:
o
Standby
180mA
o
Maximum
300mA all systems in operation (including window heater)
o
Cable Entries: 2x conduit entries 3/4” NPT or M25, with one entry plugged with a suitably
certified stopper.
o
Wiring: 14-17 AWG (2.5 - 1.0 mm
2
)