10
Performance
The following tables show test results of detection distances and times for different fire scenarios. Each table
lists results for a different sensitivity setting. For liquid fires the size of fire refers to the size of the pan, filled
with the fuel. For gas fires the length of the plume is listed
.
F-Guard-IR3-H2-HD-ASX1, F-Guard-IR3-H2-HD-ASX2 (Standard
Model)
Extreme Sensitivity
Fuel
Pan Size
Distance ft (m)
Average Response
Time (Seconds)
Methanol
1 x 1 ft
59 (18)
4.2
H
2
32-in Plume
98 (30)
1.5
Methane
32-in Plume
66 (20)
1.7
Syngas
32-in Plume
82 (25)
3.6
Medium Sensitivity
Fuel
Pan Size
Distance ft (m)
Average Response
Time (Seconds)
Methanol
1 x 1 ft
30 (9)
2.9
H
2
32-in Plume
66 (20)
1.5
Methane
32-in Plume
66 (20)
0.9
Syngas
32-in Plume
82 (25)
2.8
Low Sensitivity
Fuel
Pan Size
Distance ft (m)
Average Response
Time (Seconds)
H
2
32-in Plume
66 (20)
1.4
Methane
32-in Plume
66 (20)
1.1
Syngas
32-in Plume
82 (25)
1.1
Very Low Sensitivity
Fuel
Pan Size
Distance ft (m) Average Response
Time (Seconds)
Methanol
1 x 1 ft
10 (3)
3.6
H
2
32-in Plume
16 (5)
1.3
Methane
32-in Plume
13 (4)
0.8
Syngas
32-in Plume
13 (4)
2.2
*Syngas mixture: 50% volume methane, 50% volume hydrogen
For performance details of model 5 the following document is available, on request:
Model 5 - fast response enclosed space / automotive / spray paint booth applications F101V0024.06