PYTANIE 10 (BR2, ZA2):
The gate operates non-stop and regularly changes the direction.
Deactivate the “test mode” in the controller’s main menu.
QUESTION 11 (BR2, ZA2): Despite checking and a failure to identify
any problems in the mechanism and controller, the
device still does not operate properly. For instance, it may sometimes start or stop on its own.
1. Check whether the device receives proper voltage.
2. Check whether the devices are not powered by the same source (phase) with high distortions (the same source
powers, for instance, three-phase devices, inverters, such as elevators, escalators, boom barriers).
3. Check whether any antennas/aerials which may emit EM fields are located near the device.
4. Check for any friction in the rotor rotational movement caused by, for instance, a failure to lubricate the bearings.
QUESTION 12 (BR2, ZA2): The fuse is blown as soon as the power is on
.
When the power is off, disconnect any cables from the controller. Then restore the power to the controller and start
connecting cables one by one. A blown fuse indicates a bad component.
QUESTION 13 (BR2, ZA2): The gate stays locked when the card or chip is
brought near the access control sensor
. The gate is connected to the access
control system.
To check gate operations, activate gate unlock by shorting controller’s
1-2 or 3-4 inputs. If the gate is unlocked properly, then the problem
lies outside the device.