4. Name and Description of Each Part

NO

NAME

DESCRIPTIONS

6

RS-485 signal terminal

CN9 is Isolation RS-485 network signal connection terminal (A, B).

7

Sensor terminal

CN1 is Sensor Connection Terminal. (RD , WH , BK , BE)

8

Power lamp

When power is on, lamp lights on.

9

Trouble lamp

It lights on when there is a fault in the circuit or sensor sensitivity, etc.

10

Alarm1 lamp

It lights on when gas leaks and it exceeds Alarm1 level.

11

Alarm2 lamp

It lights on when gas leaks and it exceeds Alarm2 level.

12

Function key

During parameter setting, it changes to program mode when it is contacted with magnet-bar for 
2 sec or longer. (Program mode, Calibration mode, Test mode, etc.) Also, it is used to enter and 
set an arbitrary data.

13

Reset key

To cancel or return to the previous status during Parameter setting, use the Magnet Bar and 
touch once. (Each touch returns to the previous status by one unit.

14

↑(Up) key

During conversion of mode or number, use the Magnet-Bar and touch once. Each touch converts 
or changes one level. (Converts to the next level)

15

↓(Down) key

During conversion of mode or number, use the Magnet-Bar and touch once. Each touch converts 
or increases displayed value by one unit. (Converts to the previous level)

16

External earth

- It is an external ground for protection from external noise or strong electric field.
- Use a conductor that is 4 mm or longer when coupling ground line.

17

Mount hole

Hole to fix the gas detector on external wall or other installation sites.

18

Cover fixed screw(M4)

After assembling detector housing body and cover, they are fixed with hex lens bolt to prevent 
detachment by external shock.

19

Sensor thread

It is a mounting for gas sensor (detector).

20

Cable inlet

It is provided to supply power and inlet for measured output signal of the gas detector during 
installation work. As default, PF 3/4" is provided.

21

Internal earth

- It must be grounded to inside of detector for protection from external noise or strong electric 
field.
- Use a conductor that is 4 mm or longer when coupling ground line.

22

RS-485 Module /

HART Module (Option 사양)

It is a connector for Isolation Type RS-485 and HART network modules to communicate with PC 
or PLC. To run RS-485 network, network address must be configured. Default is 1. To run HART 
network, Polling-Address and Tag No., etc. must be configured.

23

Relay Contact 

Type Selection

Jumper

It is constructed to select A or B contact.
When it is not in ENERGIZER MODE, it operates in A contact (Normal Open) mode or B contact 
(Normal Close) mode when Jumper is connected to a part marked as A silk or B silk, respectively. 
In contrast, when it is in ENERGIZER MODE, connecting Jumper to A operates in B contact mode 
and connecting Jumper to B operates in A contact mode.

24

Warning Light Connector 

It is a connector connected when a warning light is used. (Option)

25

Program Connector

It is a connector for downloading the program for the product.

26

FRONT CASE

It is an explosion-proof case made of explosion-proof plastic and emits LED light externally 
through transparent window.

27

CASE RING

It serves as a cover to prevent deviation of front case.

28

SEXANGLE BOLT

It serves to prevent deviation after case ring assembly and is fixed by mood bolt.

29

CASE BODY

It is the main body that protects internal buzzer and other parts by body.

NO

NAME

DESCRIPTIONS

30

BUZZER

It receives signal upon an event of error and generates warning sound.

31

FIXED RING

It prevents sintering filter from escaping upon external shock.

32

FLAME ARRESTER

It blocks flow in of dust, debris, water, gas and delivers warning sound from the buzzer to 
outside.

33

ARREST CAP

It protects sinter filter from external shock.

34

LED COVER

It is a joint for LED PCB ASS'Y and covered with molding.

35

LED PCB ASS"Y

It is a multi-color LED that displays status.

36

NUT

It serves to fix parts to the compliment part.

37

SHAFT BODY

It serves to fix parts to the compliment part.

38

CABLE WIRE

It supplies power and transmits data.

[Table 1. GTD-3000ExW Transmitter Components Description]

4. Name and Description of Each Part

GTD-3000ExW

Instruction Manual

4.2. LAMP Function Description

■ In normal status, green LED lights on and buzzer does not ring.

■ When Alarm-1 signal is received, red LED flickers in 1 sec interval and buzzer rings in 1 sec interval.

■ When Alarm-2 signal is received, red LED lights on and buzzer rings continuously.

■ When Trouble signal is received, yellow LED lights on and buzzer does not ring.

Summary of Contents for GTD-3000ExW

Page 1: ...arch laboratory 23 Gunpo Advance d Industry 1 ro Bugok dong Gunpo si Gyeonggi do Tel 82 31 490 0800 Fax 82 31 490 0801 Yeongnam business office Plant 55 Gonghangap gil 85beon gil Gangseogu Busan Metropolitan City Tel 51 973 8518 Fax 51 973 8519 E mail info gastron com www gastron com ...

Page 2: ... you read it in detail and keep it well for reference when you have questions then it will give you much help The present product and the product manual can be changed without advance notice for performance improvement and use convenience of the product For accurate operation of Gas detector check up and calibrate for more than once in every 6 months See No 13 of KOSHA GUIDE P 135 2013 8 3 paragra...

Page 3: ...ta 33 11 3 Precautions during Installation 33 12 Revision History 35 1 Overview 6 2 Configuration 6 3 Specification 7 3 1 Basic Specifications 7 3 2 Mechanical Specifications 7 3 3 Electrical Specifications Standard Type 8 3 4 Environmental Specifications 8 4 Name and Description of Each Part 9 4 1 Components 9 4 2 Lamp Function Description 11 5 Installation 12 5 1 Detachment of Housing Cover 12 5...

Page 4: ...nsists of sensor that detects gas leak cable inlet and high pressure explosion proof small warning light made of SUS materials It uses magnet bar outside the main body of detector enabling calibration from the outside of the detector thus maintenance is convenient 3 1 Basic Specifications ITEMS SPECIFICATION Measuring Type Diffusion Measuring Value Display LCD or OLED Display Green Red Yellow LED ...

Page 5: ...0 NO NAME DESCRIPTIONS 1 Housing Protects Sensor and PCB Board built in the Housing from external environmental change and shock 2 Main PCB It amplifies output signal from the sensor and converts and send it as DC 4 20 mA standard output Isolation RS 485 network and alarm relay contact signals are outputted Also it sends data for the display 3 Display PCB It displays data received from main PCB on...

Page 6: ...pe RS 485 and HART network modules to communicate with PC or PLC To run RS 485 network network address must be configured Default is 1 To run HART network Polling Address and Tag No etc must be configured 23 Relay Contact Type Selection Jumper It is constructed to select A or B contact When it is not in ENERGIZER MODE it operates in A contact Normal Open mode or B contact Normal Close mode when Ju...

Page 7: ... the bottom part of the detector body 5 2 Main PCB Configuration After detaching the display parts the Main PCB terminal layout appears as shown in the figure below Table 2 Main PCB Key Part Description No NAME DESCRIPTION 1 CN11 Power Output Signal Terminal 2 CN10 Alarm Fault Relay Terminal 3 CN9 RS485 Terminal 4 J1 4 20mA Source Sink Selection Jumper ON Source Type OFF Sink Type 5 CN4 Display LC...

Page 8: ... 20mA Sink Drive J1 Jumper OFF 1 VISO VIS N C 4 20mA Sink In 2 24V 24V POWER 3 mA mA 4 20mA Source Out 4 20mA Sink Out 4 GND GND POWER 5 ETH ET EARTH Table 3 CN8 Terminal Detailed Description Figure 6 CN11 Terminal Configuration Use CVVS or CVVSB 2 0sq Shield Cable for terminal configuration To connect 4 Pin terminal from the existing old GTD 3000ExW model connect terminals in reference to pin 2 w...

Page 9: ...ration method at the Main PCB and operating setting is as follows TER NO PIN NO Terminal Name MODE Setting CN10 1 TRB OUT J2 A C Connection A Contact Normal Open J2 B C Connection B Contact Normal Close 2 TRB COM 3 AL1 OUT J3 A C Connection A Contact Normal Open J3 B C Connection B Contact Normal Close 4 AL1 COM 5 AL2 OUT J4 A C Connection A Contact Normal Open J4 B C Connection B Contact Normal C...

Page 10: ... is needed from the initial supply of operation power and it starts to operate normally after sufficient stabilization GTD 3000 Ver X XX When the power turns on model name is displayed on the first row and firmware version of the detector is displayed on the second row of LCD OLED SELFTEST 0179 Self test is performed for 3 min symbol in the second row shows the progress COMB 0 LEL It runs as below...

Page 11: ...99 00 CALIBRATION MODE CALIBRATION ZERO ZERO CALIBRATION NO YES NO ZERO GAS 0 ZERO PROCESSING SUCCESS FAIL CALIBRATION DATA 0 FAIL CALIBRATION SPAN SPAN CALIBRATION NO YES NO SPAN GAS VALUE 0 SPAN SET VALUE 50 FAIL 50 SPAN PROCESSING SUCCESS FAIL CALIBRATION DATA 0 ALARM PROGRAM MODE ALARM OPERATING AUTO MANUAL AUTO ALARM RELAY TYPE DE ENERGIZED ENERGIZED DE ENERGIZED FAULT RELAY TYPE DE ENERGIZED...

Page 12: ...ayed contact FUNC key to set the gas name and enter Program Mode GAS SEL COMB Mode that sets gas name name and contacting or key changes gas name When gas type is set to DEFIN built in gas names can be selected for use When it is set to USER the user shall set gas name using 6 character for use Characters allowed for use are number capital Alphabet space and period When position is moved by settin...

Page 13: ...Calibration Mode Contact FUNC key when CALIBRATION MODE is displayed to enter Calibration Mode Contact RESET key to return to Measuring Mode CALIBRATION SPAN Contact or key to achieve SPAN then contact FUNC key to enter Span Calibration mode SPAN CALIBRATION YES Contact or key to achieve YES then contact FUNC key to perform Span Calibration SPAN GAS VALUE O Using a calibration tool inject the stan...

Page 14: ...en a desired value is displayed contact FUNC key to set the dead band value and enter the next Alarm Program Mode ALARM1 TIME SET 1 SEC It is a mode that sets Alarm1 dwell time Contact or key to increase or decrease the value respectively Displayed number is in sec and in a range from 0 to 60 When a desired value is displayed contact FUNC key to set the alarm dwell time and enter the next Alarm Pr...

Page 15: ...ensor Module Change Sensor 3 Defective Transmitter Board ADC Change Transmitter Board 4 Defective Transmitter Board EEPROM 1 Perform Factory Initialization then correct parameter and re calibrate 2 Change sensor unit when the same problem occurs again 5 Defective MPU inside Transmitter Change Transmitter Main Board 6 Poor Sensor Output Status Change Sensor 7 Check Input Power Noise Check External ...

Page 16: ...n com 30_31 GTD 3000ExW Instruction Manual 10 Drawings and Dimensions 10 Drawings and Dimensions 10 2 Warning Light GTL 100 10 1 Standard Type Figure 14 GTL 100 Drawing Figure 13 GTD 3000ExW Standard Type Drawing ...

Page 17: ...ut are easier for leaked gas to stay the detector must be installed at the point 1 of the following Gas leak detector alarm installed outside a building shall be installed at points where gas is likely to stay in consideration to wind direction wind speed specific gravity of gas etc Gas leak detector alarm installed inside a building shall be installed near the floor when the specific gravity of g...

Page 18: ...used inlets must have safety certificates When connecting the equipment with cable screw thread must be tightened 5 threads or more Work in conditions satisfying other Standards for Selection Installation and Maintenance etc of Explosion proof Electric Machine and Equipment Wiring etc at Work Site VERSION CONTENTS DATE 0 1 Manual Initial Revision 2017 09 29 0 2 Correct typos and typographical erro...