09
GTD-5100F
Instruction Manual
4. Name and Description of Each Part
3. Specification
3.3. Electrical Specifications (Standard Type)
ITEMS
SPECIFICATION
Input Voltage(Standard)
※ Customer supplied PSU must meet
requirements IEC1010-1 and CE
Marking requirements.
Absolute min:
Nominal:
Absolute max:
Ripple maximum allowed:
18V
24V
31V
1V pk-pk
Wattage
Max. wattage:
Max. current:
7.2W @+24 VDC
300mA @+24 VDC
Analog output Current
0-20mA(500 ohms max load)
All readings ± 0.2mA
Measured-value signal:
4mA(Zero) to 20mA(Full Scale)
Fault:
0-100% LEL:
100-109%LEL:
Over 110% LEL:
Maintenance:
0mA
4mA - 20mA
20mA - 21.4mA
22mA
3mA
Analog output current ripple & noise max
±20uA
Relay contact
Alarm1, Alarm2, Fault Relay
Rated 1.0 A @ 30VDC or 0.5 A @ 125 VAC
Wiring requirement
Power
CVVS or CVVSB with shield
Analog
CVVS or CVVSB with shield
RS485
STP(Shielded Twisted Pair)
Cable Connection Length
Analog
2500m
RS485
1000m
EMC Protection:
Complies with EN50270
3.4. Environmental Specifications
ITEMS
SPECIFICATION
Operation Temperature
Transmitter
-20 to 60 ℃
Sensor
Refer to Sensor Specification
Storage Temperature
Transmitter
-20 to 60 ℃
Sensor
Refer to Sensor Specification
Operation Humidity
Transmitter
5 to 99% RH (Non-condensing)
Sensor
Refer to Sensor Specification
Pressure Range
90 to 110KPa
Max. air velocity
6m/s
4.1. Components
NO
NAME
DESCRIPTIONS
1
Case cover
Protects PCB Board and Sensor, etc built in Sensor and Housing from external environmental
change and shock.
2
Mount Holes
It is mounting hole used for fixing the product.
3
LCD display
It displays gas concentration measurements from the sensor and setting modes during parameter
settings in numbers and LED. (Refer to "Front Display Configuration" for detailed description.)
4
Power LED
When the power (DC 24V) is supplied normally, green LED lights on.
5
Trouble LED
Yellow LED lights on when it detects the sensor and flow rate to be fault. It outputs trouble relay
contact signal externally.
6
Alarm1 LED (Red)
When measured gas concentration exceeds set Alarm1 threshold, the LED lights on and relay
contact signal is outputted externally (if it is set).
(Alarm1 level can be set arbitrarily in Alarm setting mode.)
7
Alarm2 LED (Red)
When measured gas concentration exceeds set Alarm2 threshold, the LED lights on and relay
contact signal is outputted externally (if it is set).
(Alarm2 level can be set arbitrarily in Alarm setting mode.)
[Figure 2. GTD-5100F Components]