ODOR CONTROL SECTION – MEDIA BED TYPE

 

 

 

 

General Description

 

ClearAir™ units are comprised of a UL 900, MERV 16 final 

filter and a Potassium Permanganate/activated carbon 

blended module.   

    

 

 

 

Service and Maintenance

 

The Potassium Permanganate / carbon media is deep purple 

in color when new, turning to a dark brown during use and 

light tan when expended. To verify the life of the media, 

inspect the panels at scheduled service intervals consistent 

with the final filter change outs.  For additional information 

contact Green Ladder at 630-457-1872. 

 

Ordering New Media Panels: 

Green Ladder Technologies, LLC 

1502 Louis Bork Drive 

Batavia, IL 60510 

Email: 

info@greenladdertech.com

 

Phone: 630-457-1872 

 

Gaylord Odor Control System Components 

Filters

 

Smoke control filters in the odor control section of the system 

require replacement prior to them becoming loaded. It is 

recommended that the filters be inspected in accordance 

with the “Odor Control Media Inspection Frequency Chart” 

on this page, and replaced when necessary. Note that failure 

to maintain the final filter will accelerate the degradation of 

the odor media, thus a regular schedule of change outs 

needs to be established.  

Replacement filters can be purchased through Gaylord 

Industries’ partners Parts Town or Heritage Parts. 

Filter replacement part number:  

Airguard MPN VPL-0495-DOP. Filter replacements are 

dimensionally 24x24x12

. See ref 1. 

Applications servicing solid fuel cooking equipment require 

MICRO GUARD 95 MH-2958971/M2323B33-0EA750300 

replacement filters. See ref 2.  

Symptoms of excessive filter loading will be evident from a 

lack of capture performance experienced at the kitchen 

hood(s). Systems equipped with the Gaylord AirVantage will 

compensate for filter loading and issue a YELLOW service 

alert at the AirVantage command center when the filters are 

ready to be replaced.   

 

 

 

 

 

 

 

 
 

 

 

7|PAGE 

Summary of Contents for ClearAir RSPC-TPF-PCV Series

Page 1: ...maintenance can cause property damage injury or death Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment Only trained and qualified service personnel should install or service this equipment 10900 S W AVERY STREET TUALATIN OR 97062 USA PHONE 503 691 2010 TOLL FREE 800 547 9696 FAX 503 692 6048 email info gaylordventilation com www ...

Page 2: ...s of efficient effective and trouble free operation In addition this unit has undergone rigorous quality control inspections and was fully operationally tested prior to shipment If you have further questions please contact us toll free at 1 800 547 9696 or info gaylordventilation com We are more than happy to help Sincerely Gaylord Industries STREET ADDRESS 10900 S W Avery Street Tualatin Oregon 9...

Page 3: ...THIS BOOK MAY BE REPRO DUCED STORED IN A RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM BY AN ELECTRONIC MECHANICAL PHOTOCOPYING RECORD ING MEANS OR OTHERWISE WITHOUT THE WRITTEN PERMISSION OF GAYLORD INDUSTRIES 2020 The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials Additional ...

Page 4: ... OF CONTENTS RECEIVING INSTALLATION 5 HORIZONTAL INSTALLATION GUIDELINES 6 VERTICAL INSTALLATION GUIDELINES 7 SERVICE AND MAINTENANCE 8 REPLACING FILTERS AND MEDIA PANELS 9 WARRANTY Inside Back Cover 3 PAGE ...

Page 5: ...al connections to be made in the field It is recommended that the Authority Having Jurisdiction AHJ be consulted regarding local codes and installation procedures Gaylord Industries is not responsible for obtaining necessary approvals and permits which may be required for installation nor is it responsible for verifying that the unit has been installed in accordance with national state and local c...

Page 6: ...EQUIPMENT INSTALLATION HORIZONTAL MOUNTING 5 PAGE ...

Page 7: ...THIS PAGE INTENTIONALLY LEFT BLANK 6 PAGE ...

Page 8: ...r to them becoming loaded It is recommended that the filters be inspected in accordance with the Odor Control Media Inspection Frequency Chart on this page and replaced when necessary Note that failure to maintain the final filter will accelerate the degradation of the odor media thus a regular schedule of change outs needs to be established Replacement filters can be purchased through Gaylord Ind...

Page 9: ...Ref 1 Air Guard Vari Plus filter To be used on all applications except solid fuel Ref 2 MICRO GUARD 95 MH Filter used for systems serving solid fuel ODOR CONTROL SECTION MEDIA BED TYPE 8 PAGE ...

Page 10: ...anel gaskets and replace as necessary CAUTION Store access cover in a location where it will not be susceptible to damage or falling onto staff or other equipment Step 4 Remove and Inspect final filter Note filter s slide in and out of the unit through a rack Replace as necessary Replacement is required when 1 Back side of filter is contaminated 2 AirVantage Yellow Alert is present at the Command ...

Page 11: ...HIS WARRANTY All replacement parts furnished under this warranty shall be F O B Gaylord Industries of Tualatin Oregon The owner shall pay the necessary freight delivery charges and necessary labor for removal and installation of parts and any federal state or local taxes SPECIFIC ITEMS NOT COVERED BY THIS WARRANTY 1 Fan belts if equipped with an exhaust fan 2 Pre filters bag filters final filters ...

Page 12: ...FORM NO TM RSPC TPF PCV 23188 032020 2020 GAYLORD INDUSTRIES LITHO USA ...

Reviews: