2-12
Chapter 2 - Principles of Operation
ELXC-UVi Series - Cont.
Wash Cycle Sequence – Cont.
Wash Cycle Example
Extractor Wash Cycle – The Extractor Wash Cycle only comes on while the exhaust fan is on, typically dur-
ing cooking (Refer to Figure 2-12-1). Using Table T-2-16-1 on page 2-16, if the cooking equipment under the
Ventilator is Heavy Duty then the Extractor Wash would come on every 4 hours of fan operation, stay on for
3 minutes and then shut off. Refer to page 2-15 for additional details on the wash cycles.
Plenum Wash Cycle
- The Plenum Wash Cycle only comes on while the exhaust fan is off (Refer to Figure 2-12-
2). Using Table T-2-16-1 on page 2-16, if the cooking equipment under the Ventilator is Heavy Duty then the
Plenum Wash would come on every 16 hours of exhaust fan operation, stay on for 3 minutes and then shut
off. Typically the Plenum Wash Cycle will begin, if the number of fan on hours has been satisfied, immedi
-
ately after the exhaust fan has been shut off. Refer to page 2-15 for additional details on the Wash Cycles.
Figure 2-12-1
Extractor Wash On
Figure 2-12-2
Plenum Wash On
UV Lamps
Plenum Area
Extractors
Plenum Wash
Manifold
Grease Canal
Grease Gutter
Extractor Wash
Sprays
Drain
Extractor Wash
Manifold
Note: Extractor Wash
comes on only when the
Exhaust Fan is On.
Plenum Area
Plenum Wash Sprays
UV Lamps
Plenum Wash
Manifold
Grease Canal
Grease Gutter
Extractors
Drain
Extractor Wash
Manifold
Note: Plenum Wash
comes on only when the
Exhaust Fan is Off.
Summary of Contents for ELXC Series
Page 40: ...4 6 INTENTIONALLY LEFT BLANK ...
Page 74: ...7 1 Chapter 7 Wiring Diagrams ELXC GBD with AUTOSTART ...
Page 75: ...7 2 Chapter 7 Wiring Diagrams ELXC GFBD with AUTOSTART ...
Page 76: ...7 3 Chapter 7 Wiring Diagrams ELXC GBD UVi with AUTOSTART ...
Page 77: ...7 4 Chapter 7 Wiring Diagrams ELXC GFBD UVi with AUTOSTART ...
Page 83: ...A 6 INTENTIONALLY LEFT BLANK ...