background image

Vhandy technology

GCAN-2008 user manual

3. Technical Specifications

Interface characteristics

Number of outputs

8

Load types

resistive load, inductive load, lamp load;

Nominal voltage

24V DC(±20%)

output current (Max.)

500mA

Electrical isolation

500 V

GC-bus/ Signal voltage

Current consumption

120mA

Bit width

in the process image

output 1 byte

Installation position

In sequential order

Power supply

Powered by GCAN-PLC, current consumption

100mA

Environmental testing

Operating temperature

-40

~+85

Permissible relative

humidity

95%RH

no condensation

EMC test

EN 55024:2011-09
EN 55022:2011-12

Vibration/shock

resistance

EN 60068-2-6/EN 60068-2-27/29

EMC resistance burst/

ESD

EN 61000-6-2 /EN 61000-6-4

Protection class

IP 20

Basic information

Dimensions

100mm *69mm *12mm

Weight

50g

Summary of Contents for GC-2008

Page 1: ...GC 2008 8 channel digital output module PNP User manual Document version 3 02 2020 10 27...

Page 2: ...ology GCAN 2008 user manual Revision History Version Date Reason V1 00 2015 09 16 Create V2 01 2015 12 20 Modify device parameters V3 01 2017 10 22 Add parameters V3 02 2020 10 27 Modify device appear...

Page 3: ...t a glance 4 1 3 Typical application 4 2 Installation 5 2 1 Module fixing 5 2 2 Wiring method 5 2 3 System statusindicator 7 2 4 Combined with GCAN PLC 400 510series 7 2 5 Combined with GCAN 8000serie...

Page 4: ...trial automation or distributed control systems 1 2 Properties at a glance 8 output channels Nominal voltage 24V DC 20 Load types are resistive load inductive load lamp load Maximum output current 500...

Page 5: ...GC 2008 module First install the GCAN PLC on the guide rail and plug the GC 2008 along GCAN PLC s right side until the lock is stuck When remove the GC 2008 the user need to release the self locking...

Page 6: ...Vhandy technology GCAN 2008 user manual Figure 2 2 Wiring method of GC 2008 module Figure 2 3 GC 2008 module terminal definition...

Page 7: ...valid 6 Digital output 6 is valid 7 Digital output 7 is valid 8 Digital output 8 is valid Table 2 2 The GC 2008 module has no error indicator The user can determine the status through the IO RUN and...

Page 8: ...s The state of the digital output is represented by one byte with channel 8 in the high and channel 1 in the low For example when GCAN 8000 module node number is 1 the output state of channel 8 and ch...

Page 9: ...120mA Bit width in the process image output 1 byte Installation position In sequential order Power supply Powered by GCAN PLC current consumption 100mA Environmental testing Operating temperature 40 8...

Page 10: ...refully Once used it is deemed to be an endorsement and acceptance of the entire content of this statement Please strictly abide by the manual product description and related laws regulations policies...

Page 11: ...2CAN Digital input GC 1008 Digital input PNP 24V DC 8 channel GC 1018 Digital input NPN 24V DC 8 channel GC 1502 Counter 200kHz max 2 channel Digital output GC 2008 Digital output PNP 24V DC 8 channel...

Page 12: ...16 bits 10V 10V 2 channel GC 4642 Current output 16 bits 0 20mA 2 channel GC 4652 Current output 16 bits 4 20mA 2 channel GC 4662 Voltage output 16 bits 0 5V 2 channel GC 4672 Voltage output 16 bits 0...

Page 13: ...anual Sales and service Shenyang Vhandy Technology Co Ltd Address Room 401 D11 Block SISP Hunnan District Shenyang Liaoning China E mail sygckj gmail com Tel Whatsapp 86 13644001762 Skype live sygckj...

Reviews: