background image

11

Guangcheng Technology

GC-2302 user manual

3. Technical Specifications

Interface characteristics

Number of inputs

2

Pulse voltage

5V

Electrical isolation

500 V

GC-bus/ Signal voltage

Counter bit

32-bit

Installation position

In sequential order

Power supply

Powered by GCAN-PLC series,

current consumption 50mA

Environmental testing

Operating temperature

-40

~+85

Permissible relative

Humidity

95%RH

no condensation

EMC test

EN 55024:2011-09

EN 55022:2011-12

Vibration/shock

Resistance

EN 60068-2-6/EN 60068-2-27/29

EMC resistance burst/

ESD

EN 61000-6-2 /EN 61000-6-4

Protection class

IP 20

Basic information

Dimensions

100mm *69mm *12mm

Weight

50g

Summary of Contents for GC-2302

Page 1: ...GC 2302 2 channel pulse output module User manual Document version V3 03 2019 12 22...

Page 2: ...manual Revision History Version Date Reason V1 00 2015 09 16 Create V2 01 2015 12 20 Modify device parameters V3 01 2018 07 27 Add parameters V3 02 2019 11 13 Amend the new version parameters V3 03 2...

Page 3: ...1 1 Overview 4 1 2 Properties at a glance 4 1 3 Typical application 4 2 Installation 5 2 1 Module fixing 5 2 2 Wiring method 5 2 3 System status indicator 7 2 4 Method ofuse 7 3 Technical Specificatio...

Page 4: ...data in industrial automation or distributed control systems 1 2 Properties at a glance 2 pulse output channels Output pulse 5V Maximum output frequency 100kHz Electrical isolation 500 V GC bus Eachpu...

Page 5: ...on the guide rail and plug the GC 2302 along GCAN PLC s right side until the lock is stuck The GC 2302 module needs to be used with a GCAN PLC 400 510 or GCAN IO 8000 series coupler and can be powered...

Page 6: ...6 Guangcheng Technology GC 2302 user manual Figure 2 2 Wiring method of GC 2302 module Figure 2 3 GC 2302 module terminal definition...

Page 7: ...ot initialized 5 No 1 pulse output symbol flashing green light means there is pulse output if it is not on there is no pulse output 6 No 2 pulse output symbol flashing green light means there is pulse...

Page 8: ...tation ms FLEX Slope rating EN_OUT The value is 1 after successful initialization ERROR error value After the initialization function block is executed without error call the motor enable function blo...

Page 9: ...DE 1 speed mode 2 location mode 3 Pulse output mode The output pin definition of the function block EN_OUT The value is 1 after successful initialization ERROR error value Next assign values for duty...

Page 10: ...0 Device number 1 channel number 2 enable 1 send pdo 0x601 23 01 30 00 01 02 01 00 Device number 1 channel number 2 enable 0 send pdo 0x601 23 01 30 00 01 02 00 00 3 Speed control Send PDO to control...

Page 11: ...ion In sequential order Power supply Powered by GCAN PLC series current consumption 50mA Environmental testing Operating temperature 40 85 Permissible relative Humidity 95 RH no condensation EMC test...

Page 12: ...carefully Once used it is deemed to be an endorsement and acceptance of the entire content of this statement Please strictly abide by the manual product description and related laws regulations polici...

Page 13: ...M 2CAN Digital input GC 1008 Digital input PNP 24V DC 8 channel GC 1018 Digital input NPN 24V DC 8 channel GC 1502 Counter 200kHz max 2 channel Digital output GC 2008 Digital output PNP 24V DC 8 chann...

Page 14: ...ut 16 bits 10V 10V 2 channel GC 4642 Current output 16 bits 0 20mA 2 channel GC 4652 Current output 16 bits 4 20mA 2 channel GC 4662 Voltage output 16 bits 0 5V 2 channel GC 4672 Voltage output 16 bit...

Page 15: ...manual Sales and service Shenyang Guangcheng Technology Co Ltd Address No 135 21 Changqing Street Hunnan Shenyang Liaoning China E mail sygckj gmail com Tel Whatsapp 86 13644001762 Skype live sygckj W...

Reviews: