User manual  -  

VCO Series UPS 1000-3000VA 

V017 - GB

 

 

 

 

2.4.3.4 Bypass Mode 

If  the  UPS  is  unable  to  deliver  the  demanded  output  power  (most  probably  due  to  overload  or  over  temperature)  it 
automatically switches to bypass mode: the incoming mains power is channeled directly to the load. The UPS will switch 
back to normal operation when the overload has been removed or the temperature has dropped below alarm level. 

If  a  power  failure  occurs  during  this 

automatic

  bypass  mode,  the  UPS  will  most  probably  not  be  able  to  deliver  the 

demanded output power and 

output power is lost

The load can be switched to bypass manually: press the two buttons “ON/Mute” (1) and “SELECT” (2) simultaneously for 4 
seconds.  The  unit  switches  to  bypass  mode  and  symbol  “BYPASS”  (10)  is  lit.  In  this  state  the  UPS  operates  on  bypass 
regardless of the input. Press the two buttons “ON/Mute” and “SELECT” simultaneously for 4 seconds again to switch the 

UPS back to normal operation. If a power failure occurs during 

manual

 bypass mode 

output power is lost

 

2.4.3.5 ECO Mode 

For energy saving purposes the unit can be switched into ECO mode. See 2.4.5 for instructions. 
During ECO Mode, the symbol “ECO” will be lit. The UPS operates on bypass (without alarms) as long as input voltage and 
frequency are within limits. If a power failure occurs during ECO Mode the UPS switches to battery operation. If the mains 
returns the unit will switch back to ECO Mode. 
 
 

2.4.4

 

USE: SELF-TEST FUNCTION 

To start a self-test: when the UPS is in AC mode or ECO mode press the “ON/Mute” button for 4 seconds. 
The self-testing function includes load detection, battery capacity and abnormal state.  
 
 

2.4.5

 

USE: OPERATING PARAMETER SETTING 

Enter the configuration mode 

When the UPS is in Standby or operates in Bypass mode, press and hold the “SELECT” button (2) for 4 seconds.  
When the UPS enters the configuration mode, status indicator symbols will light that represent the actual parameter 
being programmed. 
Select the parameter by pressing the “ON/MUTE“ button once. 
Select the setting by pressing the “SELECT“ button once. 
Confirm the setting by pressing the “OFF/Enter” button once. 
 

Parameters and settings 

1.  Output frequency 

  50Hz 

 

 

  60Hz 

 

 

  Auto Select (default setting) 

 

2.  Output voltage 

  208V 

 

 

  220V 

 

 

  230V (default setting) 

 

 

  240V 

 

3.  ECO Mode 

  Disabled (default setting) 

 

 

  Enabled 

 

4.  Outlets group 2 

  On (default setting) 

 

 

  Off 

 

Exit the configuration mode 

Press and hold the “OFF/Enter” button (3) for 2 seconds. The UPS will return to normal operation. 
 
 

 

Summary of Contents for VCO1000

Page 1: ...erruptible Power Supply On Line VCO Series UPS 1000 2000 3000 VA GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com gimagination at work ...

Page 2: ... for future reference Model VCO Series 1000 3000 VA Issued by Product Document Department Riazzino CH Date of issue 01 09 2016 File name GE_UPS_OPM_VCO_XXX_1K0_3K0_XGB_V017 Revision 1 7 Identification No Up dating Revision Concerns Date 1 0 release initial manual 25 06 2013 1 1 branding certification 11 02 2014 1 2 buzzer behavior 25 04 2014 1 3 alarm display default output frequency 13 05 2014 1 ...

Page 3: ...ecting power and load 9 2 3 4 Connecting interface devices 9 2 3 5 Connecting EPO Emergency Power Off 9 2 4 OPERATION 10 2 4 1 Operating panel 10 2 4 2 Use Start up and switch off 11 2 4 3 Use Operating modes 11 2 4 4 Use Self test function 12 2 4 5 Use Operating parameter setting 12 2 5 COMMUNICATION 13 2 5 1 USB and RS232 communication ports 13 2 5 2 Communication card option 13 3 MAINTENANCE 14...

Page 4: ...erformed by qualified service personnel Make sure that voltage and frequency of your mains supply match the input specifications of the UPS The UPS is intended to be used in normal domestic and office situations The branch circuit supply has to be protected with a 16 A building fuse The UPS must be powered from a single phase grounded wall outlet This wall outlet must be easily accessible and clos...

Page 5: ...eries for 24 hours CAUTION In case of storage pay attention to 2 INSTALLATION 2 1 INTRODUCTION The GE General Electric VCO Series UPS a truly on line double conversion uninterruptible power supply has been designed to protect your sensitive electronic equipment such as computers and telecommunications equipment from all forms of power interference including complete power failures When the mains s...

Page 6: ... put the unit into operation Condensation may occur if the UPS system is moved directly from a cold to a warm environment The UPS system must be absolutely dry before being installed Please allow an acclimatization time of at least two hours prior to installation Save the original packing material No liability can be accepted for any transport damage when the equipment is shipped in non original p...

Page 7: ...supporting the weight We recommend that the UPS is placed in its lower half Fit the unit into the rack cabinet with the help of a second person 3 3000VA model only a battery extension pack can be connected to the UPS Remove the battery door 2 fig 2 3 2 and create an opening for the battery cable by cutting breaking off the piece indicated in figure 2 3 1 b 1 Connect the DC connector of the battery...

Page 8: ... the remaining runtime for the essential equipment connected to group 1 See 2 4 5 6 Output circuit breakers VCO3000 only In case of a severe overload the output breaker may trip The button will come out the UPS is disconnected from the mains and output power is lost In this situation reduce the load connected to the outlets of the UPS Subsequently reset the circuit breaker by pushing the button ba...

Page 9: ...g computer monitor critical data storage device etc into the appliance outlets 5 1 and 5 2 of the unit Spread the loads over the appliance outlets as equally as possible If you use a distribution box to connect more than one appliance per outlet please note that the maximum AC current rating of each appliance outlet is 7A for VCO1000 and 10A for VCO2000 VCO3000 Outlets 5 1 are always on outlets 5 ...

Page 10: ...ndicating that the battery is being discharged 6 ECO the ECO function is enabled See 2 4 3 5 MUTE the audible alarm is muted See 2 4 2 2 1 ON the appliance outlet group 1 is on This group is always on 2 ON the appliance outlet group 2 is on This group can be switched off See 2 3 2 and 2 4 5 XXX three digits show the actual value of the parameter selected IN OUT parameter shown refers to input or o...

Page 11: ...a self test 2 4 2 2 Start up the UPS mains not available If you switch on the UPS if mains power is not available the UPS is started up in battery mode it discharges the batteries The symbol BATT MODE 9 lights and an alarm sounds To mute this alarm press and hold the ON Mute button for at least 4 seconds to toggle between alarm on off This switch does not mute the alarm in case of low battery volt...

Page 12: ...into ECO mode See 2 4 5 for instructions During ECO Mode the symbol ECO will be lit The UPS operates on bypass without alarms as long as input voltage and frequency are within limits If a power failure occurs during ECO Mode the UPS switches to battery operation If the mains returns the unit will switch back to ECO Mode 2 4 4 USE SELF TEST FUNCTION To start a self test when the UPS is in AC mode o...

Page 13: ...red The interface ports are operative as soon as the mains power cord is plugged into a live wall outlet even if the UPS is switched off For more information please refer to the user manual that comes with the interface software We strongly recommend to use only original GE software products in combination with the interface ports Pin Function 1 Battery low 2 RS 232 transmission pin TXD 3 RS 232 r...

Page 14: ...rsonnel only 1 Turn off the equipment that is connected to the output sockets of the UPS 2 Turn off the UPS 3 Unplug the UPS power cord from the AC wall outlet 4 Unplug the equipment from the output sockets of the UPS 5 Remove the front panel fig 5 6 Disconnect the battery wires fig 6 7 Loosen the screws that hold the cover of the battery compartment 8 8 a VCO1000 2000 3000 Remove the battery box ...

Page 15: ...SIBLE CAUSE SOLUTION UPS will not switch on and symbol AC normal is not lit UPS line cord not connected and or UPS is not switched on Press and hold the ON Mute button for at least 2 seconds Battery voltage is too low Recharge the battery for at least 4 hours UPS always in Battery mode Power cord not connected Connect power cord Input circuit breaker tripped Reduce the load reset the circuit break...

Page 16: ...oad 60 7 8 8 General Weight kg 16 32 38 Dimensions hxwxd 88x440x405mm 88x440x620mm 88x440x620mm Enclosure protection steel plastic IP20 Communication Communication ports USB and RS232 Environment Safety IEC EN 62040 1 Electromagnetic compatibility IEC EN 62040 2 Ambient temperature 0 C 40 C Sound at 1 meter 55 dB A load and temperature dependent Maximum relative humidity 95 non condensing Filterin...

Reviews: