2.
The UPS can be used as stand alone tower format by using the two supporting stands or can be mounted in a 19
inch rack using the two mounting brackets.
2.a. Vertical installation: Tower
Assemble the two supporting stands at the bottom side of the UPS cabinet.
2.b. Horizontal installation: Rack mount
Install the two mounting brackets at the sides of the UPS cabinet.
Install the UPS into a 19 inch rack. The UPS cabinet must be supported by mounting rails, do not mount it by
using the mounting brackets only. Fix the mounting brackets on the 19 inch enclosure with screws.
CAUTION
Please consider the weight of the UPS prior to installation to ensure the rack is capable of
supporting the weight. We recommend that the UPS is placed in its lower half. Fit the unit into
the rack cabinet with the help of a second person.
3.
3000VA model only
: a battery extension pack can be connected to the UPS.
Remove the battery door (2, fig. 2.3.2) and create an opening for the battery cable by cutting/breaking off the piece
indicated in figure 2.3.1.b-1.
Connect the DC connector of the battery pack to the DC connector of the UPS. Using the DC socket of the battery
pack you can install a second, third, etc. pack. As the battery pack is equipped with an integrated battery charger it
must be connected to an AC wall outlet.
Reinstall the battery door.
To adapt the runtime prediction, re-program the new total battery capacity with the UPS monitoring software.
Please note that:
during re-programming the UPS must be in standby mode (see 2.4.2.3)
only the standard values can be set, i.e. 9/23/37/51Ah.
Fig. 2.3.1.b-2: connecting battery extension
pack to 3000VA model
Fig. 2.3.1.b-1
Fig. 2.3.1.b-3