GE Multilin
B90 Low Impedance Bus Differential System
5-17
5 SETTINGS
5.2 PRODUCT SETUP
5
•
Observer: This role has read only access to all UR settings. This role allows unlimited concurrent access but it has no
download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel.
The Factory service role is not available and is intended for factory use only.
Local Passwords
PATH: SETTINGS
PRODUCT SETUP
SECURITY
CHANGE LOCAL PASSWORDS
The Change Local Passwords menu is shown on the front panel and Enervista on a successful login of Administrator role.
The “login setting” in this menu is similar to the login setting described in
PATH: SETTINGS > PRODUCT SETUP > SECU-
RITY
except for the factory role.
Passwords are stored in text format. No encryption is applied.
Notes:
•
In Device Authentication mode, the Observer role does not have a password associated with it. In Server Authentica-
tion mode the Observer role requires a password.
•
The default password is “ChangeMe1#”.
•
Once the passwords are set, the Administrator with Supervisor approval can change the role associated password.
•
In CyberSentry, password encryption is not supported.
Session Settings
PATH: SETTINGS
PRODUCT SETUP
SECURITY
SESSION SETTINGS
The following session settings are available.
•
SESSION LOCKOUT
: This setting specifies the number of failed authentications (the default is three and the maxi-
mum is 99) before the device blocks subsequent authentication attempts for the lockout period. A value of zero means
lockout is disabled.
•
SESSION LOCKOUT PERIOD
: This setting specifies the period of time in minutes of a lockout period (the default is
three and the maximum is 9999). A value of 0 means that there is no lockout period.
Restore Defaults
PATH: SETTINGS
PRODUCT SETUP
SECURITY
RESTORE DEFAULTS
•
LOAD FACTORY DEFAULTS
: This setting is used to reset all the settings, communication and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
CHANGE LOCAL
PASSWORDS
LOGIN:
None
Range: 20 Alphanumeric Characters
MESSAGE
NEW PASSWORD:
Range: 20 Alphanumeric Characters
MESSAGE
CONFIRM PASSWORD:
Range: 20 Alphanumeric Characters
SESSION
SETTINGS
SESSION LOCKOUT:
3
Range: 0 to 99
MESSAGE
SESSION LOCKOUT
PERIOD: 3 min
Range: 0 to 9999 minutes
RESTORE DEFAULTS
LOAD FACTORY
DEFAULTS: No
Range: Yes, No
NOTE
NOTE
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...