GE Multilin
B90 Low Impedance Bus Differential System
5-39
5 SETTINGS
5.2 PRODUCT SETUP
5
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state
heartbeat
time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
setting is applicable to GSSE, fixed B90 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
GSEE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
GSSE ID
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In B90 releases previous to 5.0x, this name string was repre-
sented by the
RELAY NAME
setting.
TRANSMISSION
GENERAL
MESSAGE
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
GOOSE
GENERAL
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
Range: 1 to 60 s in steps of 1
GSSE
GSSE FUNCTION:
Enabled
Range: Enabled, Disabled
MESSAGE
GSSE ID:
GSSEOut
Range: 65-character ASCII string
MESSAGE
DESTINATION MAC:
000000000000
Range: standard MAC address
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...