5-46
B90 Low Impedance Bus Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
SERVER CONFIGURATION
The
IED NAME
and
LD INST
settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical
nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)
character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The
LOCATION
is a
variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.
The
IEC/MMS TCP PORT NUMBER
setting allows the user to change the TCP port number for MMS connections. The
INCLUDE
NON-IEC DATA
setting determines whether or not the “UR” MMS domain will be available. This domain contains a large num-
ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC
61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be
“Disabled”.
When a 0 value is involved in a change, the changes to the
IEC/MMS TCP PORT NUMBER
setting take effect when the
B90 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
The
SERVER SCANNING
feature should be set to “Disabled” when IEC 61850 client/server functionality is not required. IEC
61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If the
GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled
to increase CPU resources. When server scanning is disabled, there is no updating of the IEC 61850 logical node status
values in the B90. Clients are still able to connect to the server (B90 relay), but most data values are not updated. This set-
ting does not affect GOOSE/GSSE operation.
Changes to the
IED NAME
setting,
LD INST
setting, and GOOSE dataset take effect when the B90 is restarted.
SERVER
CONFIGURATION
IED NAME: IECDevice
Range: up to 32 alphanumeric characters
MESSAGE
LD INST: LDInst
Range: up to 32 alphanumeric characters
MESSAGE
IEC/MMS TCP PORT
NUMBER:
102
Range: 0 to 65535 in steps of 1
MESSAGE
INCLUDE NON-IEC
DATA: Enabled
Range: Disabled, Enabled
MESSAGE
SERVER SCANNING:
Disabled
Range: Disabled, Enabled
MESSAGE
LOCATION: LPHD DC PHV-
Nam Location
Range: up to 80 alphanumeric characters
MESSAGE
LATITUDE:
Range: -90.000 to 90.000 deg in steps of 0.001 deg
MESSAGE
LONGITUDE:
Range: -180.000 to 180.000 deg in steps of 0.001 deg
MESSAGE
ALTITUDE:
Range: 0 to 10,0000 m in steps of 1 m
NOTE
NOTE
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...